UT285CUNI-T UT285C Power Quality Analyzer User Manual (2)P/N:110401110254X 2021/07/06 REV.0Power Quality AnalyzerOperating Manual

UT285C Power Quality Analyzer

UNI-T UT285C Power Quality Analyzer User Manual (3)WarningUNI-T UT285C Power Quality Analyzer User Manual (4)Thank you for purchasing our UT285C Power Quality Analyzer, in order to better use this product, be sure to:--To read this user manual in detail.--To abide by the safety regulations and precautions strictly.

  • Failure to comply with these precautions may result in an electric shock, explosion, or fire.
  • Under any circ*mstance, it shall pay special attention to the safety of the use of this device.
  • Pay attention to words and symbols that stick on the panel and back of the device.
  • This measuring device is only to be used, disassembled, and repaired by qualified personnel with authorization.
  • When it may cause a hazard by continuous use for the reason of the device itself, it shall immediately stop using it and deposit it at once, leaving it for disposal by an authorized agency.
  • For the risk of danger icon in the manual "UNI-T UT285C Power Quality Analyzer User Manual (5) ", users must perform safe operations strictly in compliance with the manual content.
  • The user must strictly follow the instructions preceded by "UNI-T UT285C Power Quality Analyzer User Manual (6)"the danger symbol on the instrument and manual.
  • When removing and replacing the battery and/or the SD Card, make sure that the device is disconnected and off.
  • The current clamp must be correspondingly connected with the device, if not the test error may increase.
  • The device must not be used if the "battery/SD Card" compartment cover is missing, damaged, or incorrectly fitted.
  • The safety of any system incorporating this instrument is the responsibility of the system assembler.
  • For your safety, use only the compatible leads and accessories delivered with the instrument, which comply with IEC standard 61010-031 (2002). When sensors or accessories having a lower voltage rating and/or category are connected to the instrument, the lower voltage and/or category applies to the system so constituted.
  • Before use, check that the leads, enclosures, and accessories are in perfect condition. Any lead, sensor, or accessory of which the insulation is damaged (even partially) must be repaired or scrapped.
  • Comply with the environmental conditions (see 15.3.1)
  • We recommend using Personal Protection Equipment where required.
  • This device may be used on category IV installations for voltages that do not exceed 600 V (AC or DC) with respect to earth (as per IEC standard 61010-1), or on category III installations for voltages that do not exceed 1000 V. Never use it on networks of which the voltage or category exceeds those mentioned.
  • Use only the mains power adaptor and battery pack supplied by the manufacturer. They include specific safety features.
  • Do not reach past the physical guards on the accessories and sensors. Keep your hands away from unused terminals.
  • Some current sensors must not be placed on or removed from bare conductors at hazardous voltage.
Connection procedure:
  • Switch the instrument on.
  • Configure the device for the measurement to be made and the type of network concerned.
  • Connect the leads and current sensors to the unit.
  • Connect the earth and/or neutral lead to the network earth and/or neutral and connect the corresponding current sensor.
  • Connect the L1 phase lead to the network L1 phase and connect the corresponding current sensor. If applicable, repeat the procedure for phases L2, and L3.Note: complying with this procedure reduces connection errors to a minimum and avoids wasting time.
Disconnection procedures:
  • Proceed in the reverse of the order of connection, always finishing by disconnecting the neutral (when distributed). Disconnect the leads and switch the device off.
  • Charging the battery and uploading the test data when necessary.USB is used for data transmission, the battery can be charged by the fringe special adapter.
hom*onymous ends of the current clamp
  • The side of the current clamp marks L1, L2, L3, N/D or has a red dot is the current noninverting input, that is the hom*onymous end.
  • The side of 008B current clamp has a red dot is the current noninverting input, which is the hom*onymous end.
  • The side of 040B, 068B current clamp without screws is the current noninverting input, which is the hom*onymous end.

SUMMARY

1.1. Introduction

UT285C Power Quality Analyzer is a comprehensive test instrument carefully developed by our company and specially designed for field tests of three phases, multi-functional and intelligent, concise man-machine operation. It is easy to use, large LCD screen display, high resolution, interface in both Chinese and English, shock-proof shell structure, and so on. Can simultaneously measure the 4-channel current (ABC three-phase and neutral wire current), 4-channel voltage (ABC three-phase voltage and neutral line voltage to ground), the peak value of current voltage, maximum/minimum value over a period, three-phase imbalance factor, short-time voltage flicker, transformer K factor, active power, reactive power, apparent power, power factor and displacement power factor, active power, reactive power, apparent power, total harmonic distortion and harmonic, etc; Display real-time waveform, harmonic ratio bar charts of current-voltage; Dynamically capture the instantaneous change of voltage current, monitoring starting current, monitoring the power parameters and generate the alarm list, generate the trend chart for a long time record test data.In the current power applications, more and more large power equipment, and power grid fault have become more and more complex, with the development of the industry, it put forward high requests for more and more quality than electric energy. We provide this power quality analyzer for that, which you can troubleshoot complex power systems more quickly and accurately, and monitor and maintenance of power quality parameters more comprehensively and systemic.UT285C Power quality analyzer adopts DSP + ARM double processor architecture, DSP is used for data collection and the processing of algorithm, the ARM is used for the communication protocol and the man-machine interface processing; Analog signal acquisition is by 2 pieces AD7655 of ADI company. The resolution for AD7655 is 16 bit and it is 4-channel synchronous sampling. The highest sampling rate can reach 1 MSPS, to ensure the accuracy of the channel and the information integrity, and wouldn't miss any transient changes in the grid, can be more accurate to detect the transient waveform rising and dropping drastically, and waveform instantaneous interrupt; DSP working frequency is over 200 MHZ, to be able to timely monitoring of the power grid and dynamically adjust the sampling frequency to realize synchronization of power frequency and sampling frequency; Using a 5.6 -inch LCD color screen display, a resolution of 640 dots x 480 dots, with different display color difference between the parameters of phase, waveform, vector diagram, harmonic ratio, the user can be more efficient and more intuitive understand the state of power grid parameters. Built-in flash memory can store 60 groups of screenshots at the same time, 150 groups of capture transient voltage/current waveform figures, and 12800 groups of alarm lists. Starting current detection model can continuously capture starting current waveform for 100 s. Built-in 2G memory card to store the trend curve record, simultaneously recording 20 parameters (can choose according to to need) collect data once every five seconds, trend curve records can be stored for 300 days.Power Quality Analyzer also named: Intelligent Three Phase Power Quality Analyzer, Multifunctional Power Quality Analyzer, which is simultaneous with the functions of harmonic Analyzer, phase volt-ampere meter, and electric parameter tester. It applies to the electricity industry, petrochemical, metallurgy, railway, mining enterprises, scientific research institution, and metrological departments. Especially suitable for comprehensive analysis and diagnosis of all the voltage, current, power, power, harmonic, and phase electric parameters.

1.2. Function1.2.1. Basic functionWaveform real-time display (4 channels voltage/4 channels current).
  • True RMS values of voltages and currents.
  • The DC components of voltages.
  • Peak current and voltage values.
  • Minimum and maximum half-cycle RMS current and voltage values.
  • Pharos diagram display.
  • Measurement of each harmonic up to order 50.
  • Bar charts show harmonic ratios of the current and voltage of each phase.
  • Total harmonic distortion (THD).
  • Active, reactive, apparent power, by phase, and cumulative.
  • Active, reactive, apparent energy, by phase, and cumulative.
  • Transformer K factor.
  • Power factors (PF) and displacement factors (PDF or COS).
  • Short-term voltage flicker (PST).
  • Three-phase unbalance(current and voltage).
1.2.2. Capture function
  • Transient capture functionMonitoring instantaneous change of power grid voltage current parameters, including the voltage current fluctuations, voltage current surge, sag and short supply interruption, temporary overvoltage, impact current, and Current-voltage instantaneous distortion. Instruments can store 150 sets of transient waveforms at the same time.
  • Starting current monitoringMonitoring the surge current of the line and the startup current when electrical equipment is starting helps to correctly design capacity. Can display the RMS rising/falling curve In the startup process, the envelope curve of startup current, the waveform of 4 channels current and 4 channels voltage. Recording about 100s after the trigger, storage of the current /voltage instantaneous, and waveform curve of each cycle in 100s.
  • Trend chart recording and storing functionStore all the test parameters of basic test functions (Urms, Utd, Ucf, Uunb, Hz, Vrms, Vthd, Vcf, Vunb, PST, Arms, Athd, Acf, Aunb, KF, W, VAR, VA, PF, COS, TAN),50 voltage harmonics, 50 current harmonics. And create the trend curve. Record data for a long time according to need(concurrent selection of 20 parameters to record data once every five seconds, you can record about 300 days.).
  • Alarm functionSet the limit values according to need, monitoring the values whether overshoot, if overshoot will generate an alarm log, such as voltage, current, unbalance, harmonic ratio, frequency, active power, and total harmonic distortion. You can configure 40 different alarms, each group can set different monitoring parameters (including 50 harmonics, a total of 123 different parameters) and limit values, and also can set the shortest time of overshoot. The log can contain up to 12,800 alarms.
  • Snapshot functionAny screen can be saved (screen snapshot), at the same time automatically recording the time and test mode. Such as can save voltage and current waveform, harmonic bar charts, phasor diagrams, etc. It can save a maximum of 60 screen snapshots.
1.2.3. Other functions
  • Communication functionCommunicate with computer via USB; Monitoring software can display the waveform of the power quality analyzer, read the transient waveform, trend chart recording, alarm log, screenshots, and display on the computer.
  • Setting functionThe user can configuration of the time and date, configuration of the screen contrast and brightness, definition of each phase curve color'.Choice of type of connection to the network. Configuration of the type of current sensors and voltage ratios. Select the Chinese menu or English menu. Help menu in Chinese/English Every stage of operation can press the "help" key to obtain relevant information.
1.3. Technical specification1.3.1. Base condition and working condition
Influence factorTest itemBase conditionWorking condition
Environment temperatureAll parameters(23±2)°C-10°C— 40°C
Relative humidityAll parameters40%' 60%<80%
Phase-to-neutral voltageAll parameters(100±1%)V1.0V— 1000V
phase-to-phase voltageTrue RMS phase-to-phase voltage(200±1%)V1.0V— 2000V
CurrentTrue RMS current(5±1%)A10mA— 1000A
Network frequencyAll parameters50Hz±0.1Hz40Hz— 70Hz
Phase shiftActive power and active energyCos4=1Cosh: 0.2— 1.0
Reactive power and reactive energySin4=1Sin.: 0.2— 1.0
HarmonicAll parameters<0.1%0.0%— 100%
Voltage unbalanceAll parameters<10%0.0%— 100%
The working voltage of the deviceAll parametersDC9.8V±0.1VDC9.5V— 10.5V
External electric field, magnetic fieldAll parametersShould be avoided
Test positionMeasured related parameters of the currentTested wire at the center of clamp.
1.3.2. General specification
Power supplyRechargeable lithium-ion battery packs 9.6V, backup charger.
Battery indicatorThe battery symbol shows dump energy. When the voltage is too low, automatic shutdown after 1 minute.
Power consumptionCurrent consumption of normal test 490 mA, continuous working for 8 hours.
Display modeLCD color screen, 640dotsx480dots, 5.6 inches, display domain: 116mmx88mm.
Size of clamp068B circle current clamp: 68mmx68mm.
Instrument dimensionsLxWxH: 240m mx170mmx68 mm.
Number of channels4u/41.
Phase-to phase voltage1.0V-2000V.
Phase-to-neutral voltage1.0V-1000V.
Current068B current clamp: 1.0A-1000A;
Frequency40Hz-70Hz.
Parameters of electricityW, VA, Var, PF, DPF, cos4, tan4.
Energy parametersWh, Varh, Vah.
HarmonicOrder 0-50.
Total harmonic distortionOrder 0-50, for each phase.
Expert modeYes.
Number of Transient records150 sets.
Voltage flickerYes.
Starting current modeYes, 100 seconds.
3 phases unbalanceYes.
Record300 days(simultaneous recording 20 parameters, recording one point every 5 seconds).
Min/Max recorded valueMeasurement of maximum and minimum values over a period of time.
Alarm40 different types of parameter selections, and 12,800 sets of alarm logs.
PeakYes.
Phasor diagram displayAutomatically.
Capacity of snapshots60.
Menu languageEnglish/Chinese.
CommunicationUSB.
When an alarming campaign is initiated or a search for transients, an inrush current
Automatic switching offa capture or a trend recording is pending or in progress, the device is not automatically switching off.
In another test mode, 15 minutes without keystrokes, automatic shutdown after prompt 1 minute.
Backlight functionYes, suitable for use at night and in dark places.
WeightHost: 1.6kg (with battery).
068B circle current clamp: 510gx4;
Test wires and power adapter: 900g;
Length of voltage test wire3m.
Length of current sensor wire2m.
Working temperature and humidity-10°C-40°C; below 80%Rh.
Storage temperature and humidity-10°C-60°C; below 70%Rh.
Input impedanceThe input impedance of test voltage: 1Mi1.
Withstand voltageWithstand 3700V/SOHz sinusoidal AC voltage for 1 minute between instrument wiring and shell.
InsulationBetween instrument wiring and shell nOMO.
StructureDouble insulation, with insulation vibration-proof sheath.
Safely rulesIEC 61010 1000V Cat III / 600V CAT IV, IEC61010-031, IEC61326, Pollution degree: 2.
1.3.3. Instrument precision (excluding the current sensor)Respectively introduce the following data (on the basis of base conditions and the ideal current sensors, perfectly linear, no phase shift)
MeasurementRangeDisplay resolutionThe maximum error in the range of thereference
Frequency40Hz- 70Hz0.01Hzt(0.03)Hz
True RMS phase-to-neutral voltage1.0r 1000VMin resolution 0.1V±(0.5%+Sclgt)
True RMS phase-to-phase voltage1.0V- 2000VMin resolution 0.1V±(0.5%+5dgt)
DC voltage1.0r 1000VMin resolution 0.1V±(1.0%+5dgt)
True RMS current10mA- 1000AMin resolution lmA±(0.5%-E5dgt)
Peak of phase-to-neutralvoltage1.0r 1414VMin resolution 0.1V±(1.0%+5dgt)
Peak of phase-to-phasevoltage current peak Peak factor1.0r 2828V10mA- 1414A1.00- 3.99Min resolution 0.1VMin resolution lmA0.01±(1.0%-F5dgt)±(1.0%+Sclgt)±(1%-E2dgt)
4.00`9.990.01±(5%+2dgt)
Active power0.000W- 9999.9kWMin resolution 0.001W±(1%+3dgt)Cos00.8
t(1.5%+10dgt)0.25Cos4≥0.8
Reactive power,inductive or capacitiveApparent powerPower factor0.000VAR-9999.9 kVAR0 .000VA-9999.9kVA-1.000- 1.000Min resolution 0.001VARMin resolution 0.001VA0.001±(1%+3dgt)Sing)≥0.5
±(1.5%+10dgt)0.25Sing≥0.5±(1%+3dgt)±(1.5%+3dgt)Cos00.S
±(1.5%+10dgt)0.2≤Cos∅∠0.5
Active energy0.000Wh- 9999.9MWhMin resolution 0.001Wh±(1%+3dgt)
Coscka0.8
±(1.5%+10dgt)0.25Cos4i<0.8
Reactive energy,inductive or capacitiveApparent energy0.000VARh9999.9MVARhMin resolution0.001VARhMin resolution 0.001VAh±(1%+3dgt)Sincka0.5±(1.5%+10dgt)|0.25Sin4'<0.±(1%+3dgt)
0.000VAh-9999.9MVAh
Phase angleTan,(VAa5OVA)-179° 180°-32.76 32.761°Min resolution 0.001±(2°)1):±(1°)
The phase shift of the power factor(PDF)-1.000 1.0000.0011):±(1°)
Harmonic ratio(order 1 to 50) (Vrms>50V)Harmonic angle(Vrms>50V)0.0% 99.9%-179° 180°0.1%1°±(1%+5dgt)±(3°) harmonics of order 1 to 25±(10°) harmonics of order26 to 50
Total harmonic ratio(THD or THD-F)550Distortion factor(DF or THD-R)550Transformer K factor3 phases unbalance0.0% 99.9%0.0% 99.9%1.00 99.990.0% 100%0.1%0.1%0.010.1%±(1%+5dgt)±(1%+10dgt)±(5%)±(1%)
Type of current sensorTrue RMS currentcurrentMax error of phase angleφ
068B current clamp1.0A~ 9.9A±(2%+3dgt)±(3°)
10.0A~ 1000A±(2%+3dgt)±(2°)
Note: current clamp and instruments must be connected to the corresponding, and cannot be inserted opposite.★ The side of the current clamp marks L1, L2, L3, N/D or has a red dot is the current noninverting input, that is the hom*onymous end.★ The side of 040B, 068B current clamp without screws is the current noninverting input, that is hom*onymous end

PACKING

2.1. Standard configuration

No.DesignationQuantity
1Instrument host.1
2Instrument knapsack.1
3Current sensors4
5Testing wires.5 (yellow, green, red, blue, black)
6Crocodile clips.5
7Test probe.5
8Dedicated power adapter.1
9USB data cord.1
10Software CD.1
11Lithium battery pack.1 (Built into the instrument)
122GB memory.1 (Plug in the instrument)
13Manual, warranty card, certification.1
2.2. Weight
No.DesignationWeight
1Instrument host.1.6Kg (with battery).
2068B circle current clamp.510g×4.
3Test wires and power adapter.900g.

PRESENTATION

3.1. Overall viewUNI-T UT285C Power Quality Analyzer User Manual (7)

3.2. On/Off keyPressing UNI-T UT285C Power Quality Analyzer User Manual (8)starts the device.The device can be powered by the battery alone (if it is adequately charged) or by a specific mains power supply unit(if, in this case, the battery is also present, the power supply unit charge it).Pressing theUNI-T UT285C Power Quality Analyzer User Manual (9) key again turns the device off. Confirmation is required to turn it off if the device is in one of its recording modes or is searching for transients, alarm, and/or inrush current capture.3.3. Display screen 3.3.1. PresentationThis backlit 640×480 pixel graphic liquid crystal screen displays all measurements with their curves, the parameters of the unit, the curves selected, the instantaneous values of the signals, and the type of measurement selected When the device is powered up, it automatically displays the Waveform screen. Information about this screen can be found in §8.UNI-T UT285C Power Quality Analyzer User Manual (10)

Automatic switching off:When an alarming campaign is initiated or a search for transients, an inrush current capture, or a trend recording is pending or in progress, the device is not automatically switched off. In another test mode, 15 minutes without keystrokes, automatic switching off after prompt 1 minute.3.3.2. IconsThe display uses the following icons

IconDesignationIconsDesignation
VPhase-to-neutral voltage.UNI-T UT285C Power Quality Analyzer User Manual (11)Display of voltage and current RMS values andtheir extrema
UPhase-to-phase voltage.UNI-T UT285C Power Quality Analyzer User Manual (12)Simultaneous display of all voltage and current measurements
ACurrent.UNI-T UT285C Power Quality Analyzer User Manual (13)Display of voltage and current vector diagram.
VAApparent power.UNI-T UT285C Power Quality Analyzer User Manual (14)Energies consumed.
UNI-T UT285C Power Quality Analyzer User Manual (15)Zoom in.UNI-T UT285C Power Quality Analyzer User Manual (16)Energies generated.
UNI-T UT285C Power Quality Analyzer User Manual (17)Zoom out.UNI-T UT285C Power Quality Analyzer User Manual (18)Page screen 1 of the help function.
The X-axis cursor indicator.UNI-T UT285C Power Quality Analyzer User Manual (19)Page screen 2 of the help function.
PF…Display of PF, PDF, Tanφ.UNI-T UT285C Power Quality Analyzer User Manual (20)Page screen 3 of the help function.
W…Display of powers and energies values.UNI-T UT285C Power Quality Analyzer User Manual (21)The monitoring parameter of group 1 is in the trend mode.
UNI-T UT285C Power Quality Analyzer User Manual (22)Start Record.UNI-T UT285C Power Quality Analyzer User Manual (23)The monitoring parameter of group 2 in the trend
UNI-T UT285C Power Quality Analyzer User Manual (24)Recording list.UNI-T UT285C Power Quality Analyzer User Manual (25)The monitoring parameter of group 3 in the trend
OKValidation prompt.UNI-T UT285C Power Quality Analyzer User Manual (26)The monitoring parameter of group 4 in the trend
UNI-T UT285C Power Quality Analyzer User Manual (27)Shut down.UNI-T UT285C Power Quality Analyzer User Manual (28)Previous page screen.
UNI-T UT285C Power Quality Analyzer User Manual (29)Delete.UNI-T UT285C Power Quality Analyzer User Manual (30)Next page screen.

3.4. Keypad keys3.4.1. Function keys(yellow keys)These 6 keys UNI-T UT285C Power Quality Analyzer User Manual (31) activate the function or tool represented by the corresponding icon on the screen.3.4.2. Navigation keysA block of 4 arrow keys, a confirm key, and a return key are used for navigation in the menus

ItemFunction
UNI-T UT285C Power Quality Analyzer User Manual (32)Up direction or zoom in key.
UNI-T UT285C Power Quality Analyzer User Manual (33)Down the direction or zoom out the key.
UNI-T UT285C Power Quality Analyzer User Manual (34)Right direction or next page key.
UNI-T UT285C Power Quality Analyzer User Manual (35)Left direction or previous page key.
UNI-T UT285C Power Quality Analyzer User Manual (36)Confirms the selection.
UNI-T UT285C Power Quality Analyzer User Manual (37)Return key.
3.4.3. Mode keysThese give access to specific modes
ItemFunctionVoir
UNI-T UT285C Power Quality Analyzer User Manual (38)Waveform mode: the display of voltage and current waveforms, maxima and minima, extreme value, summary tables, voltage, and current vector diagramsUNI-T UT285C Power Quality Analyzer User Manual (39) 8
UNI-T UT285C Power Quality Analyzer User Manual (40)Harmonic mode: the display of voltage, current, and apparent power harmonic ratios (displayed in a graph), harmonic RMS value, and phase shift with respect to the fundamentalUNI-T UT285C Power Quality Analyzer User Manual (41) 7
UNI-T UT285C Power Quality Analyzer User Manual (42)Power and energy mode: displays the active power, the reactive power, the apparent power, power factor, phase shift of power factor, etcUNI-T UT285C Power Quality Analyzer User Manual (43)11
UNI-T UT285C Power Quality Analyzer User Manual (44)Trend mode: recording of the parameters selected in the Configuration menu.UNI-T UT285C Power Quality Analyzer User Manual (45)10
UNI-T UT285C Power Quality Analyzer User Manual (46)Alarm mode: listing of recorded alarms exceeding the thresholds programmed in the configuration; recording of network blackouts with half-cycle resolution (Vrms, Arms, Arms), determination of energy consumption overshoots, monitoring of compliance with a power supply quality contractUNI-T UT285C Power Quality Analyzer User Manual (47)9
UNI-T UT285C Power Quality Analyzer User Manual (48)Capture mode: monitoring the instantaneous change of power grid voltage current parameters, including the voltage current fluctuations, voltage current surge, sag and short supply interruption, temporary overvoltage, impact current, and current-voltage instantaneous distortionUNI-T UT285C Power Quality Analyzer User Manual (49)6
3.4.4. Other keysThe other keys have the following functions
ItemFunctionVoi
UNI-T UT285C Power Quality Analyzer User Manual (50)Configuration key: device configuration and capture mode parameter configuration, cansetting date and time, display, type of connection to the network, voltage ratio, currentsensor select, choice of thresholds to be detected, the definition of alarms to be detected,choice of parameters to be detectedUNI-T UT285C Power Quality Analyzer User Manual (51)5
UNI-T UT285C Power Quality Analyzer User Manual (52)Snapshot mode: a snapshot of the current screen and retrieval of screens already storedUNI-T UT285C Power Quality Analyzer User Manual (53)12
UNI-T UT285C Power Quality Analyzer User Manual (54)Help key: provides information about the functions and the symbols used for the current display modeUNI-T UT285C Power Quality Analyzer User Manual (55)13
3.5. Connectors3.5.1. Measurement input connectorsLocated on the top of the device, these connectors are distributed as followsUNI-T UT285C Power Quality Analyzer User Manual (56)3.5.2. Charging interface and USB interfaceMust be used with a special power adapter and USB cable3.6. Power supply3.6.1. Indication of battery levelThe battery icon in the top right corner of the screen shows the battery level. The number of bars is proportional to the charge level.
IconState of charge
UNI-T UT285C Power Quality Analyzer User Manual (57)Battery fully charged.
UNI-T UT285C Power Quality Analyzer User Manual (58)Low battery.
UNI-T UT285C Power Quality Analyzer User Manual (59)Mobile bars: battery charging.
UNI-T UT285C Power Quality Analyzer User Manual (60)The device is powered by mains and pre-charged.

When the battery level is too low, the following message is displayed:” Low battery, Instrument will soon turn OFF”.If you do not reconnect the device to the mains, it is switched off one minute after this message appears.3.6.2. Battery lifeBattery life is 8 hours when the battery delivered with the device is fully charged.3.6.3. Recharging the batteryThe battery is recharged by the main power unit provided, and connected to the device by the jack (Figure 3-3).Use only the main power unit provided with the instrument.Charging a fully discharged battery takes about 5 hours. When the battery is recharged, the device continues to use mains power and does not discharge the battery.3.6.4. The batteryThe device is powered by a specific lithium battery (9.6V) having a nominal capacity of 4,500 mAh.3.6.5. Mains operationThe battery is not essential when the unit is running on mains power. However, if mains power is cut off (there is no battery), during the recording process, for example, data may be lost.3.7. The standA retractable stand (Figure 3-4) on the back of the instrument keeps the device at an angle of 60° from the horizontal

UNI-T UT285C Power Quality Analyzer User Manual (61)3.8. Summary of functions 3.8.1. Measurement functions
  • The RMS values of AC voltages up to 1000 V between terminals.
  • The RMS values of AC currents up to 1000A (neutral included).
  • Sustaining voltages and currents (neutral included).
  • Minimum and maximum half-cycle RMS voltage and current.
  • Peak voltages and currents (neutral included).
  • Frequency of 50 Hz and 60 Hz networks.
  • Current and voltage peak factor (excluding neutral).
  • Calculation of the K factor (KF) (application to transformers when current harmonics are present).
  • Current and voltage distortion factor (DF) (excluding neutral).
  • Current and voltage total harmonic distortion (excluding neutral).
  • Active, reactive (capacitive and inductive), apparent power of each phase (excluding neutral).
  • Power factors (PF) and displacement power factors (PDF) (excluding neutral).
  • Short-term flicker (PST) (excluding neutral).
  • Active, reactive (capacitive and inductive), and apparent energy (excluding neutral).
  • Current and voltage harmonics (excluding neutral) up to order 50: harmonic ratio, RMS value, minimum and maximum, and sequence harmonics.
  • The apparent power of each harmonic up to order 50: harmonic ratio, RMS value, minimum and maximum.
  • The motor starting current and inrush currents
3.8.2. Main functions
  • Display of waveforms (voltages and currents).
  • Inrush Current function: displays parameters useful for the study of the starting of a motor.★ Instantaneous current at the instant designated by the cursor.★ Maximum instantaneous current (over the entire starting time).★ RMS value of the half-cycle of the current on which the cursor is positioned.★Maximum half-cycle RMS current (over the entire starting time).★Time at which starting the motor commenced.
  • Screen captures (60 maximum).
  • Transients function. Detection and recording of transients (up to 150) between the user-defined start and stop dates and times. Recording of 4 complete cycles (one before the triggering event and three after).
  • Trend recording function (2GB memory with date-stamping and user-defined start and stop dates for recording, with a maximum of 100 recordings). Display, in bar chart or curve form, the means of many parameters vs. time, with or without minima and maxima.
  • Alarm function. List of recorded alarms (up to 12,800) exceeding thresholds defined in the configuration menu.User-defined alarm monitoring starts and stops times. Display the alarm trigger channel, minimum and maximum values after the trigger, duration
3.8.3. Configuration function
  • Date and time settings.
  • Screen brightness and contrast settings.
  • Choice of curve colors.
  • Choice of reactive power and reactive energy calculation mode (with or without harmonics).
  • Choice of connection (single-phase, split-phase, 3- or 4-wire three-phase, 5-wire three-phase).
  • Choose current sensors and voltage ratio.
  • Trigger threshold values setting (voltage and current).
  • Monitoring parameters of trend diagram settings.
  • Choice of alarm monitoring parameters.
  • Erasure of data (total or partial).
  • Display software and hardware version numbers.
  • Choice of language (Chinese/English).
3.9. AbbreviationsMeanings of the symbols and abbreviations used
SymbolDesignationSymbolDesignation
UNI-T UT285C Power Quality Analyzer User Manual (62)AC and DC components.MAXMaximum true RMS.
UNI-T UT285C Power Quality Analyzer User Manual (63)AC component only.MINMinimum true RMS.
UNI-T UT285C Power Quality Analyzer User Manual (64)DC component only.msMillisecond (unit).
ΦPhase angle.PEAKMaximum (+) or minimum(-) voltage /current peak.
Inductive phase shift.PFPower factor.
UNI-T UT285C Power Quality Analyzer User Manual (65)Capacitive phase shift.PSTShort-term flicker.
°Degree.RMSTrue RMS value (current or voltage).
-.+Expert mode.TTime.
Sum of values.TanTangent.
LPhase (line).THETotal harmonic distortion.
%Percentage.Ucfphase-to-phase voltage crest factor.
AAmpere.Uhphase-to-phase voltage is harmonic.
ActCrest (peak) factor of current.TermsTrue RMS phase-to-phase voltage.
AhCurrent harmonic.USDTotal phase-to-phase voltage harmonic distortion.
AidK Factor (for transformers).Uubphase-to-phase voltage unbalance (34').
ArmsTrue RMS current.VPhase-to-neutral voltage.
AddTotal harmonic distortion of current.VAApparent power.
AuntCurrent unbalance (34').VahApparent energy.
AVGMean value.VARReactive power.
CFPeak factor (current or voltage).withReactive energy.
DCDC component (current or voltage).IfVoltage crest (peak) factor.
PDFDisplacement power factor.VrmsTrue RMS phase-to-neutral voltage.
HzFrequency of network studied.LtdTotal harmonic distortion of phase-to-neutral voltage.
KFSee Akf.VungPhase-to-neutral voltage unbalance (34').
WActive power.WhActive energy.

USE

The device must be configured in accordance with §5 before any measurements are made.The following precautions for use must be complied with:

  • Do not connect to any voltage exceeding 1,000 Vrms with respect to earth.
  • When connecting and disconnecting the battery, make sure that the measuring leads are disconnected and turned off.
Start-up

Press the UNI-T UT285C Power Quality Analyzer User Manual (66) key on the keypad to start the device.After about 3 seconds, the Waveform screen is displayed.

UNI-T UT285C Power Quality Analyzer User Manual (67)Figure 4-1: Waveform screen

The device is battery-powered only if the battery is adequately charged. If not, the alarm message “Low battery, the instrument will soon turn OFF” is displayed (see § 3.6). The device can be used with the mains power unit supplied with it connected to the jack; there is no need for the battery in this case.

Configuration

To configure the device, proceed as follows:★ With the device on, press. The configuration screen appears.★ Press UNI-T UT285C Power Quality Analyzer User Manual (68)or UNI-T UT285C Power Quality Analyzer User Manual (69) to select the parameter to be modified. Press UNI-T UT285C Power Quality Analyzer User Manual (70) to enter the selected sub-menu.

UNI-T UT285C Power Quality Analyzer User Manual (71)Figure 4-2: Configuration screen

Press UNI-T UT285C Power Quality Analyzer User Manual (72) or UNI-T UT285C Power Quality Analyzer User Manual (73)and UNI-T UT285C Power Quality Analyzer User Manual (74) or UNI-T UT285C Power Quality Analyzer User Manual (75)to browse and UNI-T UT285C Power Quality Analyzer User Manual (76) to confirm in the displayed sub-menu. See §5.3–§ 5.10 for details.Note: The following points must be checked or adapted for each measurement:
FunctionSee
Define the parameters of the calculation methods. (reactive power/ reactive energy).§5.5
Select the type of connection (single-phase to three-phase, five-wire).§5.6
Programming of the voltage ratios according to the type of current sensor connected.§5.7
Transient triggering levels (transients mode).§5.8
Values to be recorded (trend mode).§5.9
Definition of alarm thresholds.§5.10
Press UNI-T UT285C Power Quality Analyzer User Manual (77) to return to the Configuration screen.
Installation of leads

UNI-T UT285C Power Quality Analyzer User Manual (78)Connect the measuring leads to the device as follows:

  • Current measurement 4 current clamp corresponding connect to 4 channels current interfaces of L1/A, L2/B, L3/C, N/D. The current clamp muse has a corresponding connection to ensure the accuracy of measurement. Select the current clamp before measurement (see § 5.7).
  • Voltage measurement: The 5 voltage test wires according to the color corresponding connect to 5 voltage input interfaces of L1/A, L2/B, L3/C, E/GND, and N/D. Set the voltage ratio before measurement. (see § 5.7). The measuring leads must be connected to the circuit to be studied as shown by the following diagrams.
Single-phase networkUNI-T UT285C Power Quality Analyzer User Manual (79) Split-phase networkUNI-T UT285C Power Quality Analyzer User Manual (80)

Figure 4-5: Split-phase connection

3- or 4-wire three-phase networkUNI-T UT285C Power Quality Analyzer User Manual (81)5-wire three-phase networkUNI-T UT285C Power Quality Analyzer User Manual (82)Connection procedure★ Switch the instrument on.★ Configure voltage ratio, select the current sensor, and the type of network concerned.★ Connect the leads and current sensors to the unit.★ Connect the earth and/or neutral lead to the network earth and/or neutral (when distributed) and connect the corresponding current sensor.★ Connect the L1 phase lead to the network L1 phase and connect the corresponding current sensor.★ If applicable, repeat the procedure for phases L2, and L3.Note: complying with this procedure reduces connection errors to a minimum and avoids wasting time.
Waveform capture

Reminder: any screen can be saved (screen snapshot) by pressing the UNI-T UT285C Power Quality Analyzer User Manual (83) key (see § 12).With the device powered up and connected to the network (voltage measurement leads and current sensor), press UNI-T UT285C Power Quality Analyzer User Manual (84).Display of the transients modeSee §6.2.Display of the inrush current modeSee §6.3.

Display of harmonics

Reminder: any screen can be saved (screen snapshot) by pressing the UNI-T UT285C Power Quality Analyzer User Manual (85) key (see § 12).With the device powered up and connected to the network (voltage measurement leads and current sensor),press UNI-T UT285C Power Quality Analyzer User Manual (86) .Voltage harmonics displaySee §7.2.Current harmonics displaySee §7.3.

Waveform measurements

Reminder: any screen can be saved (screen snapshot) by pressing the UNI-T UT285C Power Quality Analyzer User Manual (87) key (see § 12).With the device powered up and connected to the network (voltage measurement leads and current sensor),pressUNI-T UT285C Power Quality Analyzer User Manual (88) .Display of true RMS measurementsSee §8.2.Display of measurement of total harmonic distortionSee §8.3.Display of PEAK factor measurementsSee §8.4.Display of Min and Max RMS, extreme values (voltage and current)See §8.5.Simultaneous displaySee §8.6.Display of vector diagramSee §8.7.

Alarm recording

Reminder: any screen can be saved (screen snapshot) by pressing the UNI-T UT285C Power Quality Analyzer User Manual (89) key (see § 12).With the device powered up and connected to the network (voltage measurement leads and current sensors),press UNI-T UT285C Power Quality Analyzer User Manual (90) .Configuration of alarm modeConfigure the values to be monitored as described in §9.2.Programming of an alarming campaignSee §9.3, configure start and shop time.Auto stoppageThe alarm recording campaign is stopped automatically at the Stop date and time programmed by the operator.Manual stoppageSee §9.3.3. Do not reach the preset stop date and time, the operator stop detection is active.Viewing the alarm logSee §9.4.Deleting the alarm logSee §9.5.

Trend recording

Reminder: any screen can be saved (screen snapshot) by pressing theUNI-T UT285C Power Quality Analyzer User Manual (91) key (see § 12).With the device powered up and connected to the network (voltage measurement leads and current sensors), press UNI-T UT285C Power Quality Analyzer User Manual (92).Configuring a trend parameterSee § 10.3.Programming a recordingSee § 10.2.

Energy measurements

Reminder: any screen can be saved (screen snapshot) by pressing the UNI-T UT285C Power Quality Analyzer User Manual (93) key (see § 12).With the device powered up and connected to the network (voltage measurement leads and current sensors), press UNI-T UT285C Power Quality Analyzer User Manual (94) .Measurement of energies consumedSee §11.2.Measurement of energies generatedSee §11.6.

Transfer of data to the PC

The PC software can communicate with the device through a USB interface. Upload and store the measurements for future reference.Note: The transfer does not delete the data, just copy it to the PC. When an alarming campaign is initiated or a search for transients, an inrush current capture, or a trend recording is pending or in progress, the PC cannot read the data.

Deleting data

Stored data may be deleted prior to a new test campaign, to free memory. See §5.11.

Turning off

Press the UNI-T UT285C Power Quality Analyzer User Manual (95) key to turn the device off.When an alarming campaign is initiated or a search for transients, an inrush current capture, or a trend recording is pending or in progress, the device is not automatically switched off without confirmation.The following message appears:

Are you sure want to turn OFF the instrument? Recording in progress or in standby

Select Yes or No using the UNI-T UT285C Power Quality Analyzer User Manual (96)or UNI-T UT285C Power Quality Analyzer User Manual (97)key and press UNI-T UT285C Power Quality Analyzer User Manual (98) to validate.★ If No is selected, the recording will continue.★ If Yes is selected, the data recorded until that point are saved and the device is turned off.
Power supply

Recharging the batterySee §3.6.3.Mains operationSee §3.6.5.

CONFIGURATION KEY

The UNI-T UT285C Power Quality Analyzer User Manual (99) key is used to configure the device. Before using the instrument, and thereafter as necessary, you must parameterize it. The stored configuration is retained when the instrument is switched off.

Available sub-menus

Select the sub-menu using the UNI-T UT285C Power Quality Analyzer User Manual (100)and UNI-T UT285C Power Quality Analyzer User Manual (101)keys and confirm by pressingUNI-T UT285C Power Quality Analyzer User Manual (102). To return to the main screen, press UNI-T UT285C Power Quality Analyzer User Manual (103)

UNI-T UT285C Power Quality Analyzer User Manual (104)Figure 5-1: The sub-menu display screen

NameSub-menuSee
Date/TimeDate and time settings.§5.3
DisplayScreen contrast and brightness settings.§5.4.1
Definition of voltage curve and current curve colors.§5.4.2
CalculationmethodChoice of reactive parameters (with or without harmonics).§5.5
ConnectionChoice of type of connection to the network (attention: some calculations depend upon the type of connection).§5.6
Sensor andratiosConfiguration of the ratios of the current sensors (0086 current clamps, 0406 current clamps, 068B current clamp, transformer).§5.7.1
Configuration of voltage ratios.§5.7.2
TransientmodeChoice of current thresholds to be detected.§5.8.1
Choice of voltage thresholds to be detected.§5.8.2
Trend modeChoice of parameters to be recorded for.§5.9
Alarm ModeDefinition of alarms to be detected.§5.10
Erase dataChoice of total or partial deletion of user data.§5.11
AboutSerial number, software, and hardware version numbers, and capacity of onboard memory card.§5.12
Display language

To select the display language, press the yellow key under the corresponding icon on the screen (Figure 5-1). Select zh-CN as Chinese, and choose en as English. The yellow icon indicates the current user of the language.

Date/Time

This menu defines the system date and time. The display is as follows:UNI-T UT285C Power Quality Analyzer User Manual (105)

Figure 5-2: Date/Time menu

The Date/Time field is highlighted in yellow.
  • To change the date/time, press UNI-T UT285C Power Quality Analyzer User Manual (106). The arrows UNI-T UT285C Power Quality Analyzer User Manual (107) show which value can be changed. To increment UNI-T UT285C Power Quality Analyzer User Manual (108)or UNI-T UT285C Power Quality Analyzer User Manual (109) decrement a value, press or.To select the value, press UNI-T UT285C Power Quality Analyzer User Manual (110)or UNI-T UT285C Power Quality Analyzer User Manual (111). To confirm, pressUNI-T UT285C Power Quality Analyzer User Manual (112) .
  • To modify the dating system, position the yellow cursor on the field using the UNI-T UT285C Power Quality Analyzer User Manual (113)or UNI-T UT285C Power Quality Analyzer User Manual (114)key. Press UNI-T UT285C Power Quality Analyzer User Manual (115). The arrows UNI-T UT285C Power Quality Analyzer User Manual (116) show which value can be changed.Select DD/MM/YY or MM/DD/YY or YY/MM/DD, press UNI-T UT285C Power Quality Analyzer User Manual (117)or UNI-T UT285C Power Quality Analyzer User Manual (118), then confirm by pressing UNI-T UT285C Power Quality Analyzer User Manual (119).
To return to the Configuration main menu, pressUNI-T UT285C Power Quality Analyzer User Manual (120) .
Display

Contrast/BrightnessThis menu is used to define the contrast and brightness of the display unit. The display is as follows:UNI-T UT285C Power Quality Analyzer User Manual (121)

Figure 5-3: The Contrast/Brightness menu

The selected field is highlighted in yellow.
  • To modify the contrast, press UNI-T UT285C Power Quality Analyzer User Manual (122)or UNI-T UT285C Power Quality Analyzer User Manual (123) .
  • To move to the next field, press UNI-T UT285C Power Quality Analyzer User Manual (124)or UNI-T UT285C Power Quality Analyzer User Manual (125) .
  • To change the brightness, press UNI-T UT285C Power Quality Analyzer User Manual (126)or UNI-T UT285C Power Quality Analyzer User Manual (127) .
To return to the Configuration menu, press UNI-T UT285C Power Quality Analyzer User Manual (128).ColorsThe UNI-T UT285C Power Quality Analyzer User Manual (129) menu is used to define the colors of the voltage and current curves. The colors available are yellow, orange, red, pink, brown, green, and dark green, blue, sky blue, dark blue, light grey, and grey.The display is as follows:UNI-T UT285C Power Quality Analyzer User Manual (130)

Figure 5-4: The Colours menu

The selected field is highlighted in yellow.
  • To select the color of the voltage and current curves, press UNI-T UT285C Power Quality Analyzer User Manual (131)or UNI-T UT285C Power Quality Analyzer User Manual (132) .
  • To move to the next field, press UNI-T UT285C Power Quality Analyzer User Manual (133)or UNI-T UT285C Power Quality Analyzer User Manual (134) .
To return to the Configuration menu, press UNI-T UT285C Power Quality Analyzer User Manual (135)
Calculation methods

UNI-T UT285C Power Quality Analyzer User Manual (136) determines whether or not harmonics are used in calculating the reactive parameters (powers and energies).

UNI-T UT285C Power Quality Analyzer User Manual (137)Figure 5-5: The Calculation methods menu

  • To select With harmonics or Without harmonics, press UNI-T UT285C Power Quality Analyzer User Manual (138)or UNI-T UT285C Power Quality Analyzer User Manual (139)UNI-T UT285C Power Quality Analyzer User Manual (140)
Connection

The UNI-T UT285C Power Quality Analyzer User Manual (141) menu is used to define how the device is connected, according to the type of network.UNI-T UT285C Power Quality Analyzer User Manual (142)

Figure 5-6: The Connection menu

Several electrical diagrams can be selected:To configure the type of connection, proceed as follows:
  • Select Single-Phase, Two-Phase, 3- or 4-wire Three-Phase, or 5-wire Three-Phase by pressing UNI-T UT285C Power Quality Analyzer User Manual (143)or UNI-T UT285C Power Quality Analyzer User Manual (144).To return to the Configuration menu, press UNI-T UT285C Power Quality Analyzer User Manual (145)
Sensors and ratios

Current sensors and ratiosThe UNI-T UT285C Power Quality Analyzer User Manual (146) menu, invoked by the yellow key A icon, defines the current sensors and ratios. The device can select 3 current sensors, meanwhile, it can choose an optional current transformer, and set the turn ratio according to to need.

UNI-T UT285C Power Quality Analyzer User Manual (147)

Figure 5-8: Current clamp and ratios screen in the Sensors and ratios menu

The possibilities are:
UNI-T UT285C Power Quality Analyzer User Manual (148)008B current clamp: 10mA~ 10A
UNI-T UT285C Power Quality Analyzer User Manual (149)040B current clamp: 0.10A~ 100A
UNI-T UT285C Power Quality Analyzer User Manual (150)068B current clamp: 1.0A~ 1000A
UNI-T UT285C Power Quality Analyzer User Manual (151)300F Flexible Coil Current Sensor (with Integrator) : 10A ~ 3000A
If using the optional current transformer, should be configured as follows:
  • Set transformer turns ratio: Into ratio setting, pressUNI-T UT285C Power Quality Analyzer User Manual (152) .To select each field, use the UNI-T UT285C Power Quality Analyzer User Manual (153)or UNI-T UT285C Power Quality Analyzer User Manual (154), To modify the turns ratio, use the UNI-T UT285C Power Quality Analyzer User Manual (155)or UNI-T UT285C Power Quality Analyzer User Manual (156) , (such as 2000/0001, device input 25mA, display 50.0A).
  • To validate, pressUNI-T UT285C Power Quality Analyzer User Manual (157) .
Note: selecting optional transformer, device current port forbade input more than 500mA.Voltage ratiosThe UNI-T UT285C Power Quality Analyzer User Manual (158) menu, invoked by the V icon, defines the voltage ratios.UNI-T UT285C Power Quality Analyzer User Manual (159)

Figure 5-9: The Voltage Ratios screen in the Sensors and ratios menu

All the channels ratio can be set as the following:
  • (4V, 1/1) 4 channels with are 1:1 ratio.
  • (4V) 4 channels are the same ratio.
  • (3V+VN)L1\L2\L3 is the same ratio, N line independent setting ratio.
  • (V1+V2+V3+VN)4 channels independent setting ratio respectively.★ To configure the ratios, press UNI-T UT285C Power Quality Analyzer User Manual (160), then use the UNI-T UT285C Power Quality Analyzer User Manual (161)key and validate by pressing UNI-T UT285C Power Quality Analyzer User Manual (162)★ To select the values, use the UNI-T UT285C Power Quality Analyzer User Manual (163)or UNI-T UT285C Power Quality Analyzer User Manual (164) key (highlighted in yellow).★ To setting the ratio, press UNI-T UT285C Power Quality Analyzer User Manual (165), The arrows UNI-T UT285C Power Quality Analyzer User Manual (166)appear.★ To select the value, press UNI-T UT285C Power Quality Analyzer User Manual (167)or UNI-T UT285C Power Quality Analyzer User Manual (168). To increment or decrement a value, press UNI-T UT285C Power Quality Analyzer User Manual (169)or UNI-T UT285C Power Quality Analyzer User Manual (170) , then press UNI-T UT285C Power Quality Analyzer User Manual (171) to confirm.
To return to the Configuration main menu, press UNI-T UT285C Power Quality Analyzer User Manual (172).
Transient mode

The UNI-T UT285C Power Quality Analyzer User Manual (173) mode is used to configure the voltage and current thresholds.Current thresholdsThe UNI-T UT285C Power Quality Analyzer User Manual (174) screen, displayed by pressing the A icon, is used to define the current thresholds.UNI-T UT285C Power Quality Analyzer User Manual (175)

Figure 5-10: The Current thresholds screen in the Transient Mode menu

★ The arrow indicatesthe channel of a cursor.★ Use the UNI-T UT285C Power Quality Analyzer User Manual (176)or UNI-T UT285C Power Quality Analyzer User Manual (177) key to go from one channel to another, press UNI-T UT285C Power Quality Analyzer User Manual (178) appear UNI-T UT285C Power Quality Analyzer User Manual (179) , and start to change.★ Press UNI-T UT285C Power Quality Analyzer User Manual (180)or select the change bit and threshold current unit(mA/A), To increment or decrement a value, press UNI-T UT285C Power Quality Analyzer User Manual (181)or UNI-T UT285C Power Quality Analyzer User Manual (182)★ Press UNI-T UT285C Power Quality Analyzer User Manual (183) to confirm.Voltage thresholdsThe UNI-T UT285C Power Quality Analyzer User Manual (184) screen, displayed by pressing the V icon, is used to define the voltage thresholds.All the voltage thresholds can be set as the following:
  • (4V)4 channels are the same threshold.
  • (3V+VN)L1\L2\L3 is the same threshold, N line independent setting threshold.
  • (V1+V2+V3+VN) 4 channels independent setting threshold respectively.
UNI-T UT285C Power Quality Analyzer User Manual (185)

Figure 5-11: The Voltage thresholds screen in the Transient Mode menu

★ Press UNI-T UT285C Power Quality Analyzer User Manual (186) to enter ratio configure, and the arrows appear. Use UNI-T UT285C Power Quality Analyzer User Manual (187)or UNI-T UT285C Power Quality Analyzer User Manual (188)to select the above 3 different threshold combinations, then press UNI-T UT285C Power Quality Analyzer User Manual (189) to confirm.★ To select the threshold, use the UNI-T UT285C Power Quality Analyzer User Manual (190)or UNI-T UT285C Power Quality Analyzer User Manual (191)key (highlighted in yellow).★ To setting the threshold, press UNI-T UT285C Power Quality Analyzer User Manual (192) , The arrows appear and start to change.★ Press UNI-T UT285C Power Quality Analyzer User Manual (193)orUNI-T UT285C Power Quality Analyzer User Manual (194) select the change bit and threshold unit(V/kV), To increment or decrement a value, press UNI-T UT285C Power Quality Analyzer User Manual (195)or UNI-T UT285C Power Quality Analyzer User Manual (196). Then press UNI-T UT285C Power Quality Analyzer User Manual (197) to confirm.To return to the Configuration main menu, press UNI-T UT285C Power Quality Analyzer User Manual (198)
Trend mode

The device has a recording function – key UNI-T UT285C Power Quality Analyzer User Manual (199) - (see § 10) for recording measured and calculated values (Urms, Vrms, Arms, etc.). Four independent configurations can be parameterized, depending on needs.To select the desired configuration, press the yellow key corresponding to the UNI-T UT285C Power Quality Analyzer User Manual (200) icon. The active configuration is identified by the icon with a yellow background.A configuration example is shown below:

UNI-T UT285C Power Quality Analyzer User Manual (201)

Figure 5-12: In this example, only the Urms values are recorded in configuration 1

★ To define configuration 1, press the yellow key on the keypad corresponding to the UNI-T UT285C Power Quality Analyzer User Manual (202) icon. The icon appears on yellow ground.★ To select the values, move the yellow cursor using the UNI-T UT285C Power Quality Analyzer User Manual (203)or UNI-T UT285C Power Quality Analyzer User Manual (204) and UNI-T UT285C Power Quality Analyzer User Manual (205)or UNI-T UT285C Power Quality Analyzer User Manual (206).★ Press UNI-T UT285C Power Quality Analyzer User Manual (207) to select/unselect, the red solid dot indicates is selected, the red hollow dot indicates is unselected.The recordable values are:
UnitDesignation.
TermsTrue RMS phase-to-phase voltage.
USDHarmonic distortion of the phase-to-phase voltage(2φ, 3φ).
UcfCrest (peak) factor of phase-to-phase voltage(2φ, 3φ).
UubPhase-to-phase voltage unbalance(2φ, 3φ).
HzNetwork frequency.
VrmsTrue RMS phase-to-neutral voltage.
LtdTotal harmonic distortion of the phase-to-neutral voltage.
IfCrest factor of phase-to-neutral voltage.
VungPhase-to-neutral voltage unbalance(2φ, 3φ).
PSTShort-term flicker.
ArmsTrue RMS current.
AddTotal harmonic distortion of the current.
ActCrest factor of current.
AuntCurrent unbalance (2φ, 3φ).
KFK factor.
WActive power.
VARReactive power.
VAApparent power.
PFPower factor.
PDFDisplacement power factor.
TanTangent.
?See the comment below.
Features specific to the last two lines. These are recalled below:UNI-T UT285C Power Quality Analyzer User Manual (208)

Figure 5-13: These two lines involve harmonics

These two lines involve the recording of the harmonics of VAh, Ah, Vh, and Uh. You can select a range of orders of the harmonics to be recorded (between 0 and 50) for each of these quantities, and within this range, if desired, only odd harmonics. Proceed as follows:
  • To enter the value to be recorded: with the line highlighted in the yellow, pressUNI-T UT285C Power Quality Analyzer User Manual (209) . The arrows UNI-T UT285C Power Quality Analyzer User Manual (210) appear. Select the value (VAh, Ah, Vh, and Uh) for which harmonics are to be recorded by pressing UNI-T UT285C Power Quality Analyzer User Manual (211)or UNI-T UT285C Power Quality Analyzer User Manual (212)“?” indicate is unselected. Confirm by pressing . The values field is highlighted in yellow.Press UNI-T UT285C Power Quality Analyzer User Manual (213) to go to the next field.
  • Select the starting harmonic order: with the field highlighted in yellow. Press UNI-T UT285C Power Quality Analyzer User Manual (214), and the arrows UNI-T UT285C Power Quality Analyzer User Manual (215) appear. Press UNI-T UT285C Power Quality Analyzer User Manual (216)or UNI-T UT285C Power Quality Analyzer User Manual (217)to increment or decrement the harmonic order, then validate by pressing. Press UNI-T UT285C Power Quality Analyzer User Manual (218) to go to the next field.
  • Select the last harmonic: (greater than or equal to the starting harmonic order) highlighted in yellow. Press UNI-T UT285C Power Quality Analyzer User Manual (219) , and The arrows UNI-T UT285C Power Quality Analyzer User Manual (220) appear. Press UNI-T UT285C Power Quality Analyzer User Manual (221)or UNI-T UT285C Power Quality Analyzer User Manual (222)to increment or decrement the harmonic order, then validate by pressing.Press UNI-T UT285C Power Quality Analyzer User Manual (223) to go to the next field.
  • Odd harmonics only: to select or deselect this function, press UNI-T UT285C Power Quality Analyzer User Manual (224) . The solid red dot identifies your selection:Selected, only odd harmonics between the two orders of harmonics specified in the previous points are recorded.Not selected, all harmonics (even and odd) between the two orders of harmonics specified in the previous points are recorded.

UNI-T UT285C Power Quality Analyzer User Manual (225)Figure 5-14: record-setting harmonic order

To return to the Configuration main menu, press UNI-T UT285C Power Quality Analyzer User Manual (226)Proceed in the same way to define the other configurations.
Alarm mode

The UNI-T UT285C Power Quality Analyzer User Manual (227) screen defines the alarms used by the Alarm Mode function (see § 9). You can configure 40 different alarms.UNI-T UT285C Power Quality Analyzer User Manual (228)

Figure 5-15: The Alarm mode menu

  • Use the UNI-T UT285C Power Quality Analyzer User Manual (229)or UNI-T UT285C Power Quality Analyzer User Manual (230) key to select a different setting alarm parameter group.To select the field, pressUNI-T UT285C Power Quality Analyzer User Manual (231) . The arrows UNI-T UT285C Power Quality Analyzer User Manual (232) appear.
  • To select the values (Vah, Ah, Uh, etc., see table in § 5.9), press UNI-T UT285C Power Quality Analyzer User Manual (233)or UNI-T UT285C Power Quality Analyzer User Manual (234) , then confirm withUNI-T UT285C Power Quality Analyzer User Manual (235) . The field is highlighted in yellow.
  • To navigate horizontally in the fields, use the UNI-T UT285C Power Quality Analyzer User Manual (236)or UNI-T UT285C Power Quality Analyzer User Manual (237)keys, then confirm by pressing UNI-T UT285C Power Quality Analyzer User Manual (238). The arrows UNI-T UT285C Power Quality Analyzer User Manual (239) appear. Enter the values by pressing UNI-T UT285C Power Quality Analyzer User Manual (240)or UNI-T UT285C Power Quality Analyzer User Manual (241) , then confirm by pressing. Do the same for all values to be entered in the fields.For each alarm to be defined, select:★ The type of alarm (Vah, Ah, Uh, Vh, Tan, PF, PDF, VA, VAR, W, Athd, Utd, Vthd, KF, Hz, Aunb, Vunb, Vrms, Acf, Ucf, Vcf, PST, Arms, Arms, and Vrms – see the table of abbreviations in § 3.9).★ The orders of harmonics (between 0 and 50, for Vah, Ah, Uh, and Vh).★ The alarm filter (3L: 3 phases, L1, L2, L3 can be triggered individually; N: neutral can be triggered).★ The direction of the alarm (> or < for Arms, Urms, Vrms, Hz only; otherwise only one direction is possible).★ The triggering threshold of the alarm (the prefix of the unit of the alarm can be set in the following cases: W, VAR, VA, Arms, Arms, Vrms).★ The minimum duration above or below the threshold required for alarm validation(can be set from 0 seconds to 99 minutes.★ The hysteresis (The percentage increase or decrease from the corresponding alarm threshold, optional values are 1%, 2%, 5%, or 10%. If more than this percentage will stop the alarm - See § 17.2).
  • Press UNI-T UT285C Power Quality Analyzer User Manual (242) to select or cancel the alarm parameter set, the red solid dot indicate is selected, the red hollow dot indicates is unselected.
  • To display different alarm screen pages, press the yellow buttons corresponding to the UNI-T UT285C Power Quality Analyzer User Manual (243) icons.
  • To return to the Configuration menu, pressUNI-T UT285C Power Quality Analyzer User Manual (244) .
Erase memory

The UNI-T UT285C Power Quality Analyzer User Manual (245) menu partially or totally deletes the data recorded in the device (trend recording, transients recording, inrush current, alarm, screen snapshots, device setting, and monitoring parameter setting).

UNI-T UT285C Power Quality Analyzer User Manual (246)

Figure 5-16: Erase memory menu

  • For a partial deletion:★ Select the parameters you want to delete by pressing the UNI-T UT285C Power Quality Analyzer User Manual (247)or UNI-T UT285C Power Quality Analyzer User Manual (248) key. The selected field is highlighted in yellow.★ Press UNI-T UT285C Power Quality Analyzer User Manual (249) to select/unselect, the red solid dot indicates is selected, and the red hollow dot indicates is unselected.Note: If the Configuration is selected, the message “after the configuration is deleted, the device will be turned off” appears on the screen.★ Select the submenu by pressing the yellow key corresponding to the UNI-T UT285C Power Quality Analyzer User Manual (250) icon. The UNI-T UT285C Power Quality Analyzer User Manual (251) icon displayed yellow indicates ready to delete, then press the yellow key corresponding to the icon to cancel the delete state.★ In the state of ready to delete, press UNI-T UT285C Power Quality Analyzer User Manual (252) to confirm the deletion.
To return to the Configuration main menu, press UNI-T UT285C Power Quality Analyzer User Manual (253).
  • To delete everything:★ Select All parameters by pressing the yellow key on the keypad corresponding to the UNI-T UT285C Power Quality Analyzer User Manual (254) icon. The selection is identified by the red marks.Note: Since the Configuration is selected, the message “after the configuration is deleted, the device will be turned off” appears on the screen.★ To uncheck all items selected, press the yellow key on the keypad corresponding to the UNI-T UT285C Power Quality Analyzer User Manual (255) icon, the red hollow dot indicates is unselected.
To return to the Configuration main menu, press UNI-T UT285C Power Quality Analyzer User Manual (256).
About

The screen displays the serial number of the device, the firmware version, the DSP software version, the icon version, and the SD card capacity.UNI-T UT285C Power Quality Analyzer User Manual (257)

Figure 5-17: The About menu

To return to the Configuration menu, press UNI-T UT285C Power Quality Analyzer User Manual (258)

WAVEFORM CAPTURE KEY

Available sub-modes

The sub-modes are listed on the screen below and covered individually in the paragraphs that follow.UNI-T UT285C Power Quality Analyzer User Manual (259)

Figure 6-1: The screen when the Waveform Capture mode is entered

To enter the sub-modes, proceed as follows:★ Select the mode by using the UNI-T UT285C Power Quality Analyzer User Manual (260)or UNI-T UT285C Power Quality Analyzer User Manual (261)key. The selected field is highlighted in yellow.★ Confirm by pressing UNI-T UT285C Power Quality Analyzer User Manual (262).To return to the Waveform capture screen, press UNI-T UT285C Power Quality Analyzer User Manual (263).
Transient mode

The UNI-T UT285C Power Quality Analyzer User Manual (264) model is used to record transients, view the list of recorded transients, and if necessary delete them. You can record up to 150 transients.UNI-T UT285C Power Quality Analyzer User Manual (265)

Figure 6-2: The Detection schedule screen in the Transients mod

6.2.1. Programming and starting a searchPressing the yellow key corresponding to theUNI-T UT285C Power Quality Analyzer User Manual (266) icon. The Detection schedule screen is displayedUNI-T UT285C Power Quality Analyzer User Manual (267)6.2.1.1. Stage 1: configuration of parameter★ Select the Start field using theUNI-T UT285C Power Quality Analyzer User Manual (268)or UNI-T UT285C Power Quality Analyzer User Manual (269) key. The selected field is highlighted in yellow. PressUNI-T UT285C Power Quality Analyzer User Manual (270) to enter the values. The arrows▲▼ appear in the start date and time field of the programming of a campaign.★ PressUNI-T UT285C Power Quality Analyzer User Manual (271)or UNI-T UT285C Power Quality Analyzer User Manual (272)to increment or decrement a value andUNI-T UT285C Power Quality Analyzer User Manual (273)or UNI-T UT285C Power Quality Analyzer User Manual (274)to go to the next item.Note: The start date and time must be later than the current date and time.★ PressUNI-T UT285C Power Quality Analyzer User Manual (275)to validate the programmed Start date and time.★ Select the Stop field using theUNI-T UT285C Power Quality Analyzer User Manual (276)or UNI-T UT285C Power Quality Analyzer User Manual (277) key. The selected field is highlighted in yellow. PressUNI-T UT285C Power Quality Analyzer User Manual (278) to enter the values. The arrows▲▼ appear in the Stop date and time field of the programming of a campaign.★ PressUNI-T UT285C Power Quality Analyzer User Manual (279)or UNI-T UT285C Power Quality Analyzer User Manual (280) to increment or decrement a value andUNI-T UT285C Power Quality Analyzer User Manual (281)or UNI-T UT285C Power Quality Analyzer User Manual (282)to go to the next item.Note: The stop date and time must be later than the start date and time.★ PressUNI-T UT285C Power Quality Analyzer User Manual (283)to validate the programming of the Stop date and time.★ Instruments can store 150 sets of Transient records at the same time.Proceed in the same way for the Count. The count can contain up to 150 transient records.Proceed in the same way for Series name fields. The available alphanumeric characters are the uppercase letter from A to Z and the digits from 0 to 9. File name length up to eight characters.★ To configure the voltage thresholds and current thresholds, press the yellow shortcutUNI-T UT285C Power Quality Analyzer User Manual (284)key to return to theConfiguration menu.To return to the Waveform capture screen, pressUNI-T UT285C Power Quality Analyzer User Manual (285).6.2.1.2. Stage 2: starting the programTo begin monitoring the start and stop times you have defined, press the yellow key on the keypad corresponding to the OK icon.
  • The OK icon disappears and theUNI-T UT285C Power Quality Analyzer User Manual (286) icon appears instead.
  • The message Detection on standby is displayed until the start time is reached and the iconflashes in the screen’s top display bar.
  • When the start time is reached the message Detection in progress is displayed.
  • When the stop time is reached, the Detection schedule screen with the OK icon (bottom right-hand corner of the screen) is displayed again. It is then possible to program another search.Note: voltage and/or current transients are recorded according to the activation thresholds configured. If activation occurs on the current threshold, the current and voltage waveforms are recorded.To return to the Waveform capture screen, pressUNI-T UT285C Power Quality Analyzer User Manual (287).
6.2.1.3 . Intentional transients campaign stoppage

The search can be stopped deliberately before the stop date and time by pressing the yellow key on the keypad corresponding to theUNI-T UT285C Power Quality Analyzer User Manual (288)icon (bottom right corner of the screen). The OK icon then reappears in the same place.6.2.2. Display a transientTo display the recorded transients, proceed as follows

UNI-T UT285C Power Quality Analyzer User Manual (289)Figure 6-4: the Transient list screen

★ Select the line of the transient to be displayed using the or key. The selected field is bolded. Confirm by pressingUNI-T UT285C Power Quality Analyzer User Manual (290). The screen displays the transients in the form of curvesUNI-T UT285C Power Quality Analyzer User Manual (291)★ Select the curve to be displayed using theUNI-T UT285C Power Quality Analyzer User Manual (292)or UNI-T UT285C Power Quality Analyzer User Manual (293)key, and move the cursor using the UNI-T UT285C Power Quality Analyzer User Manual (294)or UNI-T UT285C Power Quality Analyzer User Manual (295), long press can move quickly.To return to the Transient list screen, pressUNI-T UT285C Power Quality Analyzer User Manual (296).6.2.3. Delete a transientTheUNI-T UT285C Power Quality Analyzer User Manual (297)icon is displayed only if a record has been made. To delete a transient, proceed as follows: UNI-T UT285C Power Quality Analyzer User Manual (298)★ Select the transient to be deleted using theUNI-T UT285C Power Quality Analyzer User Manual (299)or UNI-T UT285C Power Quality Analyzer User Manual (300) key. The selected field is bolded.★ Select the submenu by pressing the yellow key corresponding to theUNI-T UT285C Power Quality Analyzer User Manual (301)icon. TheUNI-T UT285C Power Quality Analyzer User Manual (302) icon displayed yellow indicates ready to delete, then press the yellow key corresponding to theUNI-T UT285C Power Quality Analyzer User Manual (303) icon orUNI-T UT285C Power Quality Analyzer User Manual (304) cancel the delete state.★ In the state of ready to delete, pressUNI-T UT285C Power Quality Analyzer User Manual (305)to confirm the deletion.6.3. Starting current modeThis mode is used to capture (record) inrush currents (voltage and current waveforms). In capture display mode, two sub-menus, RMS and PEAK, are available (see § 6.3.2).The device keeps in memory only a single current inrush capture.6.3.1. Programming the captureTo program the capture of an inrush current, select the submenu by pressing the yellow key of the keypad corresponding to theUNI-T UT285C Power Quality Analyzer User Manual (306)icon. The Capture schedule screen is displayed. UNI-T UT285C Power Quality Analyzer User Manual (307)6.3.1.1. Stage 1: configuration of parameterProceed as follows:★ Select the Start threshold field using the orUNI-T UT285C Power Quality Analyzer User Manual (308)or UNI-T UT285C Power Quality Analyzer User Manual (309) key. The selected field is highlighted in yellow. PressUNI-T UT285C Power Quality Analyzer User Manual (310) to enter the type of values. The arrowsUNI-T UT285C Power Quality Analyzer User Manual (311) appear in the Start threshold field.★ PressUNI-T UT285C Power Quality Analyzer User Manual (312)or UNI-T UT285C Power Quality Analyzer User Manual (313) to increment or decrement a value and pressUNI-T UT285C Power Quality Analyzer User Manual (314)or UNI-T UT285C Power Quality Analyzer User Manual (315) to go to the next item.★ PressUNI-T UT285C Power Quality Analyzer User Manual (316)to confirm Proceed in the same manner for the Triggering filter, Hysteresis, and Start time.Note: for more information on hysteresis, refer to § 17.2.6.3.1.2. Stage 2: starting the captureTo start the capture program at the start date and time you have defined press the yellow key on the keypad corresponding to the OK icon.

★ The OK icon disappears and theUNI-T UT285C Power Quality Analyzer User Manual (317) icon appears instead.★ The message capture pending is displayed until the start time is reached and theUNI-T UT285C Power Quality Analyzer User Manual (318)icon flashes in the screen’s upper display bar.★ When the start conditions are met and the start time is reached, the message Capture in progress is displayed and the memory occupation indicator appears at the top of the creek. (The black bar represents memory used; the white bar represents memory available.) The indicator is displayed only during the capture and disappears when the capture is completed.★ If the capture is completed with a stop event (see conditions in § 17.5) or if the recording memory of the device is full, the capture stops automatically. Programming the capture mode and OK icon reappear.Note: the device can keep in memory only a single inrush current capture. If you wish to make another capture, first, delete the previous one.To return to the Waveform capture screen, pressUNI-T UT285C Power Quality Analyzer User Manual (319).6.3.1.3. Intentional stoppage of captureA capture can be stopped deliberately by pressing the yellow key on the keypad corresponding to the icon (bottom right corner of the screen). OK, the icon will appear in the same place.6.3.2. Displaying the parameter of the captureTo display the characteristics of the capture, proceed as follows:

  • Select the submenu by pressing the yellow key corresponding to theUNI-T UT285C Power Quality Analyzer User Manual (320) icon. The Capture parameters screen is displayed.
UNI-T UT285C Power Quality Analyzer User Manual (321)
No.FunctionSee
-1RMS modeUNI-T UT285C Power Quality Analyzer User Manual (322)6.3.3
-2PEAK modeUNI-T UT285C Power Quality Analyzer User Manual (323) 6.3.4
  • Choose the type of display, RMS or PEAK, by pressing the yellow key corresponding to the icon. The device displays waveforms (current and voltage) on which you can move the time cursor and zoom in and out.★ The instantaneous current and voltage at the time indicated by the cursor★ The maximum instantaneous current (over the entire capture).★ The RMS current in the half-cycle on which the cursor is positioned.★ The maximum half-cycle RMS current (over the entire capture).★ Maximum instantaneous value PEAK(over the entire starting time).★ The starting time and the motor starting period.
Caution: The voltage must be present before the inrush current is proper for a stable and correct frequency lock.6.3.3. True RMS current and voltageThe RMS mode displays the record of the trend of the true half-cycle RMS current and voltage and the frequency trend curve.6.3.3.1. The 3A RMS display screenThe following information is displayed:UNI-T UT285C Power Quality Analyzer User Manual (324)6.3.3.2. The L1 RMS display screenThe following information is displayed:UNI-T UT285C Power Quality Analyzer User Manual (325)Note: Filters L2 and L3 display the trend of the true half-cycle RMS current and voltage of phases 2 and 3. The screen is identical to the one displayed for filter L1.6.3.4. Instantaneous inrush currentThe PEAK mode is used to display the envelopes and waveforms of the inrush current capture.6.3.4.1. The 4A PEAK display screenThe following information is displayed:UNI-T UT285C Power Quality Analyzer User Manual (326)6.3.4.2. The A1 PEAK display screenUNI-T UT285C Power Quality Analyzer User Manual (327)Note: Filters A2 and A3 display the record of the current envelope of phases 2 and 3. The screen is identical to the one displayed for filter A1.

HARMONICS MODE

The UNI-T UT285C Power Quality Analyzer User Manual (328)key displays a representation of the harmonic ratios of the voltage, current, and apparent power, order by order. It can be used to determine the harmonic currents produced by nonlinear loads and analyze problems caused by harmonics according to their order (overheating of neutrals, conductors, motors, etc.).

7.1. Available sub-menusThe submenus are listed on the screen below and described individually in the paragraphs that follow.The measurement type is selected using the yellow keys of the keypad below the screen. UNI-T UT285C Power Quality Analyzer User Manual (329)7.2. Phase-to-neutral voltageTheUNI-T UT285C Power Quality Analyzer User Manual (330) sub-menu displays the harmonics of the phase-to-neutral voltage.Note: The choice of curves to be displayed depends on the type of connection (see § 5.6):★ Single-phase: no choice (L1).★ Two-phase: 2L, L1, L2.★Three-phase, 3-, 4-, or 5-wire: 3L, L1, L2, L3, -,+ ( expert mode).The screen snapshots shown as examples were obtained with a three-phase connection. This observation also applies to the other sub-menus.7.2.1. The 3L phase-to-neutral harmonics display screenThe following information is displayed:UNI-T UT285C Power Quality Analyzer User Manual (331)Display in expert mode (three-phase connection only - See UNI-T UT285C Power Quality Analyzer User Manual (332) 7.6) of the 3 phases (3×3L) or of L1, L2, or L3(*).7.2.2. The L1 phase voltage harmonics display screenThe following information is displayed:UNI-T UT285C Power Quality Analyzer User Manual (333)Note: Filters L2 and L3 display the harmonics of the phase-to-neutral voltage for phases 2 and 3, respectively. The screen is identical to the one displayed for filter L1.7.3. CurrentTheUNI-T UT285C Power Quality Analyzer User Manual (334) sub-menu displays the harmonics of the current.7.3.1. The 3L current harmonics display screenThe following information is displayed:UNI-T UT285C Power Quality Analyzer User Manual (335)7.3.2. The L1 current harmonics display screenThe following information is displayed:UNI-T UT285C Power Quality Analyzer User Manual (336)Note: Filters L2 and L3 display the current harmonics of phases 2 and 3, respectively. The screen is identical to the one displayed for filter L1.7.4. Apparent powerThe UNI-T UT285C Power Quality Analyzer User Manual (337)sub-menu displays the harmonics of the apparent power.7.4.1. The 3L apparent power harmonics display screenThe information is: UNI-T UT285C Power Quality Analyzer User Manual (338)7.4.2. The L1 apparent power harmonics display screenThe information is:UNI-T UT285C Power Quality Analyzer User Manual (339)Note: Filters L2 and L3 display the apparent power of the harmonics for phases 2 and 3, respectively. The screen is identical to the one displayed for filter L1.7.5. Phase-to-phase voltageThe UNI-T UT285C Power Quality Analyzer User Manual (340)sub-menu is available only for three-phase connections when the voltage ratios of phases 1, 2, and 3 are equal. This sub-menu displays the harmonics of the phase-to-phase voltage.7.5.1. The 3L phase-to-phase voltage harmonic display screenThe following information is displayed:UNI-T UT285C Power Quality Analyzer User Manual (341)7.5.2. The L1 phase-to-phase voltage harmonics display screenThe following information is displayed:UNI-T UT285C Power Quality Analyzer User Manual (342)

7.6. Expert modeTheUNI-T UT285C Power Quality Analyzer User Manual (343) model is available with a three-phase connection only when the ratios of the three phases are equal. It UNI-T UT285C Power Quality Analyzer User Manual (344)is used to display the influence of the harmonics on the heating of the neutral and rotating machines. To display expert mode press theUNI-T UT285C Power Quality Analyzer User Manual (345)or UNI-T UT285C Power Quality Analyzer User Manual (346) keys of the keypad. The selection is highlighted in yellow and the screen simultaneously displays the expert mode.From this screen, two sub-menus,UNI-T UT285C Power Quality Analyzer User Manual (347)and UNI-T UT285C Power Quality Analyzer User Manual (348), are available (see next page).7.6.1. The phase-to-phase voltage expert mode display screenThe UNI-T UT285C Power Quality Analyzer User Manual (349)sub-menu displays the influence of the harmonics of the phase-to-neutral voltage on the heating of the neutral and rotating machines.The following information is displayed:UNI-T UT285C Power Quality Analyzer User Manual (350)

7.6.2. The current expert mode display screenThe UNI-T UT285C Power Quality Analyzer User Manual (351)sub-menu displays the influence of the harmonics of the current on the heating of the neutral and rotating machines.The following information is displayed:UNI-T UT285C Power Quality Analyzer User Manual (352)

WAVEFORM KEY

TheUNI-T UT285C Power Quality Analyzer User Manual (353) key is used to display the current and voltage curves, along with the values measured and those calculated from the voltages and currents (except for power, energy, and harmonics).8.1. Available sub-menusThe sub-menus are listed on the screen below and described individually in the paragraphs that follow.The type of measurement is selected using the yellow keys on the keypad below the screen.UNI-T UT285C Power Quality Analyzer User Manual (354)8.2. Measurement of the true RMS valueThe UNI-T UT285C Power Quality Analyzer User Manual (355)sub-menu displays the waveforms over one period of the signals measured and the true RMS voltage andcurrent.Note: The choice of curves to be displayed depends on the type of connection (see § 5.6):

  • Single-phase: no choice (L1)
  • Two-phase: 2V, 2A, L1, L2
  • Three-phase, 3- or 4-wire: 3U, 3V, 3A, L1, L2, L3
  • Three-phase, 5-wire:
★ For UNI-T UT285C Power Quality Analyzer User Manual (356): 3U, 3V, 3A, L1, L2, and L3★ ForUNI-T UT285C Power Quality Analyzer User Manual (357) : 3U, 4V, 4A, L1, L2, L3, and NThe screen snapshots shown as examples are those obtained with a three-phase 5-wire connection.8.2.1. The 3U display screenThis screen displays the three phase-to-neutral voltages of a three-phase system.The following information is displayed:UNI-T UT285C Power Quality Analyzer User Manual (358)8.2.2. The 4V RMS display screenThis screen displays the three phase-to-neutral voltages and the neutral-to-earth voltage of a three-phase system.The following information is displayed:UNI-T UT285C Power Quality Analyzer User Manual (359)8.2.3. The 4A RMS display screenThis screen displays the three-phase currents and the neutral current of a three-phase system.The following information is displayed:UNI-T UT285C Power Quality Analyzer User Manual (360)8.2.4 The RMS display screen for neutralThis screen displays the neutral voltage with respect to the earth and the neutral current.The following information is displayed:UNI-T UT285C Power Quality Analyzer User Manual (361)Note: L1, L2, and L3 display the current and voltage in phases 1, 2, and 3, respectively. The screen is identical to the one displayed for the neutral.8.3. Measurement of total harmonics distortionTheUNI-T UT285C Power Quality Analyzer User Manual (362)sub-menu displays the waveforms of the signals measured over one full cycle and the total voltage and current harmonic distortion.8.3.1. The 3U display screenThis screen displays the phase-to-phase voltage waveforms for one period and the total harmonic distortion values.The following information is displayed:UNI-T UT285C Power Quality Analyzer User Manual (363)8.3.2. The 3V display screenThis screen displays the phase-to-neutral voltage waveforms for one period and the total harmonic distortion values.The following information is displayed:UNI-T UT285C Power Quality Analyzer User Manual (364)8.3.3. The 3A display screenThis screen displays the phase current waveforms for one period and the total harmonic distortion values.The following information is displayed:UNI-T UT285C Power Quality Analyzer User Manual (365)Note: L1, L2, and L3 display the total current and voltage harmonic distortion for phases 1, 2, and 3, respectively.8.4. Measurement of the PEAK factorTheUNI-T UT285C Power Quality Analyzer User Manual (366)sub-menu displays the waveforms of the signals measured over one period and the voltage and current peak factors.8.4.1. The 3U CF display screenThis screen displays the phase-to-phase voltage waveforms of one period and the peak factors.The following information is displayed: UNI-T UT285C Power Quality Analyzer User Manual (367)8.4.2. The 3V display screenThis screen displays the phase-to-neutral voltage waveforms of one period and the peak factors.The following information is displayed:UNI-T UT285C Power Quality Analyzer User Manual (368)8.4.3. The 3A CF display screenThis screen displays the current waveforms of one period and the peak factors.The following information is displayed:UNI-T UT285C Power Quality Analyzer User Manual (369)Note: L1, L2, and L3 display the current and voltage peak factors for phases 1, 2, and 3, respectively.8.5. Measurement of extreme and mean voltage and currentThe UNI-T UT285C Power Quality Analyzer User Manual (370)sub-menu displays the maximum and minimum RMS voltage and current and the instantaneous positive and negative peak voltage and current.8.5.1. The 3U Max.Min. -display screenThis screen displays the maximum and minimum RMS values and the instantaneous positive and negative phase-to-phase voltage peaks.The following information is displayed:UNI-T UT285C Power Quality Analyzer User Manual (371)Note: The MAX. and MIN. RMS measurements are calculated every half cycle (i.e. every 10 ms for a 50-Hz signal).The measurements are refreshed every 300 ms.8.5.2. The 4V Max.-Min. display screenThis screen displays the maximum and minimum RMS values and the instantaneous positive and negative peaks of the phase-to-neutral voltages and of the neutral.The following information is displayed: UNI-T UT285C Power Quality Analyzer User Manual (372)Note: The Max. and Min. RMS measurements are calculated every half cycle (i.e. every 10 ms for a signal at 50 Hz). The measurements are refreshed every 300 ms.8.5.3. The 4A Max.-Min. display screenThis screen displays the maximum and minimum RMS values and the positive and negative instantaneous peak values of the phase and neutral currents.The following information is displayed: UNI-T UT285C Power Quality Analyzer User Manual (373)

Note: The Max. and Min. RMS measurements are calculated every half cycle (i.e. every 10 ms for a signal at 50 Hz).The measurements are refreshed every 300 ms.8.5.4. The L1 Max.-Min. display screenThis screen displays the mean, maximum, and minimum RMS values and the instantaneous positive and negative peaks of the phase-to-neutral voltage and of the current of phase 1.The following information is displayed:UNI-T UT285C Power Quality Analyzer User Manual (374)

Note: The Max. and Min. RMS measurements are calculated every half cycle (i.e. every 10 ms for a signal at 50 Hz).The measurements are refreshed every 300 ms.L2, L3, and N display the maximum and minimum RMS values and the instantaneous positive and negativepeaks of the phase-to-neutral voltage and of the current for phases 2, 3, and of the neutral-to-earth. The screen is identical to the one displayed for the L1.8.6. Simultaneous displayThe UNI-T UT285C Power Quality Analyzer User Manual (375)sub-menu displays all of the voltage and current measurements (RMS, DC, THD, DF, CF, PST, and KF).8.6.1. 3U simultaneous display screenThis screen displays the RMS, DC, THD, DF, and CF values of the phase-to-phase voltages.The following information is displayed:UNI-T UT285C Power Quality Analyzer User Manual (376)8.6.2. 4V simultaneous display screenThis screen displays the RMS, DC, THD, DF, CF, and PST values of the phase-to-neutral voltages and of the neutral.The following information is displayed:UNI-T UT285C Power Quality Analyzer User Manual (377)8.6.3. 4A simultaneous display screenThis screen displays the RMS, DC, THD, DF, CF, and KF values of the phase and neutral currents.The following information is displayed:UNI-T UT285C Power Quality Analyzer User Manual (378)8.6.4. L1 simultaneous display screenThis screen displays the RMS, DC, THD, DF, CF, and KF values of the phase and neutral currents.The following information is displayed:UNI-T UT285C Power Quality Analyzer User Manual (379)Note: L2 and L3 provide the simultaneous display of the current and voltage for phases 2 and 3, respectively.8.6.5. Screen for simultaneous display of neutralThis screen displays the RMS voltage and current of the neutral, the DC component of the neutral voltage.

8.7. Display of phasor diagramTheUNI-T UT285C Power Quality Analyzer User Manual (380) sub-menu displays a vector representation of the fundamentals. It indicates their associated quantities: the modulus of the vectors, phases, and unbalances of the voltages and currents.8.7.1. The 3V phasor diagram display screenThis screen displays a vector representation of the fundamentals. It indicates their associated quantities: the modulus of the vectors and unbalances of the phase-to-neutral voltages, the phase angle of phase-to-neutral voltage with respect to current.The following information is displayed:UNI-T UT285C Power Quality Analyzer User Manual (381)

8.7.2. The 3U phasor diagram display screenThis screen displays a vector representation of the fundamentals. It indicates their associated quantities: the modulus of the vectors, phase angle, and unbalances of the phase-to-phase voltages.The displayed information is identical to that described in § 8.7.1 but relative to the phase-to-phase voltages.8.7.3. The 3A phasor diagram display screenThis screen displays a vector representation of the fundamentals. It indicates their associated quantities: the modulus of the vectors, phase angle, and unbalances of the currents.The displayed information is identical to that described in § 8.7.1 but relative to the current.8.7.4. The L1 phasor diagram display screenThis screen displays a vector representation of the fundamentals. It indicates their associated quantities: the modulus of the vectors of voltage and current of phase 1, phase angle of voltage with respect to the current of phase1. The following information is displayed: UNI-T UT285C Power Quality Analyzer User Manual (382)

Note: L2 and L3 display a vector representation of the fundamentals. It indicates their associated quantities: the modulus of the vectors of voltage and current of phases 2 and 3, respectively, and the phase angle of voltage with respect to the current of phases 2 and 3, respectively.

ALARM MODE KEY

The UNI-T UT285C Power Quality Analyzer User Manual (383)mode detects overshoots of thresholds (Vrms, Arms, Arms, PST, Vcf, Ucf, Acf, Vunb, Aunb, Hz, KF, Vth, And, Add, |W|, |VAR|, VA, |cos Φ|, |PF|, |tan Φ| Vh, Uh, Ah, and |VAh|) programmed in the configuration mode.The user should program an alarm threshold (hysteresis) first and then start the alarm campaign. The values to be monitored:★were defined by the Configuration / Alarm mode screen (see § 5.10).★select the setting parameters (the red solid dot indicates selected, and the red hollow dot indicates not selected).You can capture over 12,800 alarms. Stored alarms can subsequently be transferred to a PC to save (see the corresponding manual).9.1. Available submenusThe submenus are listed on the screen below and described individually in the paragraphs that follow.The sub-menus are selected using the yellow keys on the keypad below the screen.UNI-T UT285C Power Quality Analyzer User Manual (384)The OK andUNI-T UT285C Power Quality Analyzer User Manual (385) icons have the following functions:★OK: Validating the programming of a campaign and starting the alarm campaign (see § 9.3.2).★UNI-T UT285C Power Quality Analyzer User Manual (386): Voluntary stoppage of alarm campaign (see § 9.3.3).9.2. Alarm mode configurationTheUNI-T UT285C Power Quality Analyzer User Manual (387)submenu displays the list of alarms configured (see § 5.10). This shortcut key lets you define or change alarm configurations.The following information is displayed:UNI-T UT285C Power Quality Analyzer User Manual (388)Reminder: Use theUNI-T UT285C Power Quality Analyzer User Manual (389)or UNI-T UT285C Power Quality Analyzer User Manual (390) keys to browse vertically in the fields. Use the UNI-T UT285C Power Quality Analyzer User Manual (391)or UNI-T UT285C Power Quality Analyzer User Manual (392)keys to browse horizontally in the fields.Proceed as follows to configure an alarm:★ Select the field by pressingUNI-T UT285C Power Quality Analyzer User Manual (393). The arrows appear.★ Enter values by pressing or, then validate via. The field is highlighted in yellow.Do the same for all values to be entered in the fields.★ Activate the configured alarm by placing the yellow cursor on the browsing column and pressingUNI-T UT285C Power Quality Analyzer User Manual (394). The red solid dot indicates selected. When the condition is met the alarm can be triggered, generating the alarm log.Note: To deactivate the alarm, repeat the last step.★Press UNI-T UT285C Power Quality Analyzer User Manual (395)to return to the Programming a campaign screen.9.3. Programming an alarming campaignTheUNI-T UT285C Power Quality Analyzer User Manual (396) submenu is used to specify the start and stop times for an alarming campaign.UNI-T UT285C Power Quality Analyzer User Manual (397)9.3.1. Stage 1: programming the start/stop timesProceed as follows:★ Select the Start field using theUNI-T UT285C Power Quality Analyzer User Manual (398)or UNI-T UT285C Power Quality Analyzer User Manual (399) key. The selected field is highlighted in yellow. PressUNI-T UT285C Power Quality Analyzer User Manual (400)to enter the values. The arrowsUNI-T UT285C Power Quality Analyzer User Manual (401) appear in the start date and time campaign programming field.PressUNI-T UT285C Power Quality Analyzer User Manual (402)or UNI-T UT285C Power Quality Analyzer User Manual (403)to increment or decrement a value and UNI-T UT285C Power Quality Analyzer User Manual (404)or UNI-T UT285C Power Quality Analyzer User Manual (405)to move to the next item.Note: The start date and time must be after the current date and time.★ PressUNI-T UT285C Power Quality Analyzer User Manual (406)to validate the programming of the Start date and time.★ Select the Stop field using the UNI-T UT285C Power Quality Analyzer User Manual (407)or UNI-T UT285C Power Quality Analyzer User Manual (408) key. The selected field is highlighted in yellow. PressUNI-T UT285C Power Quality Analyzer User Manual (409)to enters thevalues. The arrowsUNI-T UT285C Power Quality Analyzer User Manual (410)appear in the Stop date and time campaign programming field. PressUNI-T UT285C Power Quality Analyzer User Manual (411)or UNI-T UT285C Power Quality Analyzer User Manual (412)to increment or decrement a value and UNI-T UT285C Power Quality Analyzer User Manual (413)or UNI-T UT285C Power Quality Analyzer User Manual (414) to move to the next item.Note: The Stop date and time must be after the start date and time.★Press UNI-T UT285C Power Quality Analyzer User Manual (415)to validate the programming of the Stop date and time.9.3.2. Stage 2: Starting the alarm campaignPress the yellow key corresponding to the OK icon to start the alarm campaign between the start and stop times you specified.

  • The OK icon disappears and theUNI-T UT285C Power Quality Analyzer User Manual (416) icon appears in its place.
  • The Campaign on standby message is displayed while awaiting the start time and theUNI-T UT285C Power Quality Analyzer User Manual (417)icon blinks in the screen'stop display bar.
  • The Campaign running message is displayed when the Start time is reached.
  • The Campaign schedule screen and OK icon are displayed when the Stop time is reached. You can then program another campaign.

9.3.3. Voluntary stoppage of alarm campaignThe alarm campaign can be voluntarily stopped before the Stop date and time by pressing the yellow key corresponding to theUNI-T UT285C Power Quality Analyzer User Manual (418)icon (bottom right-hand corner of the screen). The OK icon then reappears in its place.

9.4. Viewing the alarm logTheUNI-T UT285C Power Quality Analyzer User Manual (419)submenu displays the alarm log. The log can contain up to 12,800 alarms. Press the yellow key corresponding to theUNI-T UT285C Power Quality Analyzer User Manual (420)icon to view this alarm log.Note: the type of connection selected in theUNI-T UT285C Power Quality Analyzer User Manual (421)mode does not affect which alarm filters can be chosen and which parameters are monitored. Users are responsible for these choices.The following information is displayed:UNI-T UT285C Power Quality Analyzer User Manual (422)Reminder: At the alarm log, the default units of monitored parameters corresponding to the trigger threshold and trigger amplitude are as follows:Table 9-1
Monitored parametersDefaultunitsUnits with the suffixExample
ArmsAm: express mAk: express kA2.5: express 2.5A423m: express 423mA
Vrms/UrmsVk: express kV326: express 326V1.2k: express 1.2kV
W/VAR/VAW/Var/VAK: express kW/kVar/kVAM: express MW/MVar/MVAW parameter: 315 express 315WW parameter: 5.8k express 5.8kW
HzHz50.00: express 50.00Hz
9.5. Deleting the alarm logTheUNI-T UT285C Power Quality Analyzer User Manual (423)submenu is used to delete the whole log. To do this, proceed as follows:Select the submenu by pressing the yellow key corresponding to theUNI-T UT285C Power Quality Analyzer User Manual (424) icon. The icon displayed yellow indicates ready to delete, then press the yellow key corresponding to theUNI-T UT285C Power Quality Analyzer User Manual (425) icon to cancel the delete state. TheUNI-T UT285C Power Quality Analyzer User Manual (426) icon displayed in gray indicates don't delete.In the state of ready to delete, pressUNI-T UT285C Power Quality Analyzer User Manual (427)to delete the whole alarm log. The log is empty.UNI-T UT285C Power Quality Analyzer User Manual (428)

TREND MODE KEY

The UNI-T UT285C Power Quality Analyzer User Manual (429)mode records changes to parameters previously specified in the Configuration/Trend mode screen (see § 5.9).10.1. Available sub-menusThe sub-menus are listed on the screen below and described individually in the paragraphs that follow.The sub-menus are selected using the yellow keys on the keypad below the screen.UNI-T UT285C Power Quality Analyzer User Manual (430)The OK icon confirms the programming of a recording (see § 10.2).10.2. Programming and start recordingThe UNI-T UT285C Power Quality Analyzer User Manual (431)submenu specifies the parameters of a new recording campaign. UNI-T UT285C Power Quality Analyzer User Manual (432)10.2.1. Stage 1: programming of parametersProceed as follows:★ Select the Configuration field using theUNI-T UT285C Power Quality Analyzer User Manual (433)or UNI-T UT285C Power Quality Analyzer User Manual (434) keys. The selected field is highlighted in yellow. PressUNI-T UT285C Power Quality Analyzer User Manual (435)to enters the type of configuration. The arrowsUNI-T UT285C Power Quality Analyzer User Manual (436) appear.★ Select the configuration to be used by browsing using theUNI-T UT285C Power Quality Analyzer User Manual (437)or UNI-T UT285C Power Quality Analyzer User Manual (438) keys. PressUNI-T UT285C Power Quality Analyzer User Manual (439)to validate.Reminder: ConfigurationsUNI-T UT285C Power Quality Analyzer User Manual (440)toUNI-T UT285C Power Quality Analyzer User Manual (441) were defined in the Configuration / Trend mode screen (see § 5.9). The configuration procedure is also described in § 10.3.★ Select the Start field using the UNI-T UT285C Power Quality Analyzer User Manual (442)or UNI-T UT285C Power Quality Analyzer User Manual (443) keys. The selected field is highlighted in yellow. Press UNI-T UT285C Power Quality Analyzer User Manual (444)to enter the values. The arrows UNI-T UT285C Power Quality Analyzer User Manual (445)appear in the recording start date and time programming field. Press UNI-T UT285C Power Quality Analyzer User Manual (446)or UNI-T UT285C Power Quality Analyzer User Manual (447) increment or decrement a value and UNI-T UT285C Power Quality Analyzer User Manual (448)or UNI-T UT285C Power Quality Analyzer User Manual (449) switch year, month, day, hour, or minute.Note: The start date and time must be later than the current date and time.★ PressUNI-T UT285C Power Quality Analyzer User Manual (450)to validate the programming of the Start date and time.★ Select the Stop field using the UNI-T UT285C Power Quality Analyzer User Manual (451)or UNI-T UT285C Power Quality Analyzer User Manual (452) keys. The selected field is highlighted in yellow. Press UNI-T UT285C Power Quality Analyzer User Manual (453)to enter the values. The arrows UNI-T UT285C Power Quality Analyzer User Manual (454)appear in the recording stop date and time programming field. Press UNI-T UT285C Power Quality Analyzer User Manual (455)or UNI-T UT285C Power Quality Analyzer User Manual (456) increment or decrement a value andUNI-T UT285C Power Quality Analyzer User Manual (457)or UNI-T UT285C Power Quality Analyzer User Manual (458)to switch year, month, day, hour, or minute.Note: The stop date and time must be later than the start date and time. The longest recording time can be programmed see § 10.6.4.★Press UNI-T UT285C Power Quality Analyzer User Manual (459)to validate the programming of the Stop date and time.★Select the Period field using theUNI-T UT285C Power Quality Analyzer User Manual (460)or UNI-T UT285C Power Quality Analyzer User Manual (461) keys and pressUNI-T UT285C Power Quality Analyzer User Manual (462) to enter the value. The arrowsUNI-T UT285C Power Quality Analyzer User Manual (463) appear.★Press UNI-T UT285C Power Quality Analyzer User Manual (464)or UNI-T UT285C Power Quality Analyzer User Manual (465)to increment or decrement the possible values (1 s, 5 s, 20 s, 1 min, 2 min, 5 min, 10 min, or 15 min).★PressUNI-T UT285C Power Quality Analyzer User Manual (466) to validate.Note: The recording interval period is the time over which the measurements of each recorded value are averaged (arithmetic mean). That is how often a data record is.★ PressUNI-T UT285C Power Quality Analyzer User Manual (467)or UNI-T UT285C Power Quality Analyzer User Manual (468) to highlight the Name box in yellow and pressUNI-T UT285C Power Quality Analyzer User Manual (469)to enter edit mode. Enter the name of the recording (not more than 8 characters, records shall use a different name, file name intermediate cannot appear spaces).The available alphanumeric characters are the uppercase letters from A to Z and the digits from 0 to 9. Use theUNI-T UT285C Power Quality Analyzer User Manual (470)or UNI-T UT285C Power Quality Analyzer User Manual (471) keys to display a character andUNI-T UT285C Power Quality Analyzer User Manual (472)or UNI-T UT285C Power Quality Analyzer User Manual (473)to move to the adjacent character.★PressUNI-T UT285C Power Quality Analyzer User Manual (474) to validate the name.10.2.2. Stage 2: starting a programmed recording

  • Press the yellow key corresponding to the OK icon (bottom right-hand corner of the screen) to begin recording between your specified start and stop times.The OK icon disappears and theUNI-T UT285C Power Quality Analyzer User Manual (475) icon appears in its place.
  • The Recording on standby message is displayed while awaiting the start time and theUNI-T UT285C Power Quality Analyzer User Manual (476)icon blinks in the screen’s top display bar.
  • The Recording running message is displayed when the start time is reached.
UNI-T UT285C Power Quality Analyzer User Manual (477)
  • The Recording schedule screen and OK icon (bottom right-hand corner of the screen) reappear when the stoptime is reached. The OK icon then reappears in its place.
10.2.3. Voluntary stoppage of recording in progressRecording can be voluntarily stopped before the stop date and time by pressing the yellow key corresponding to theUNI-T UT285C Power Quality Analyzer User Manual (478) icon (bottom right-hand corner of the screen). The OK icon then reappears in its place.10.3. Trend mode configurationTheUNI-T UT285C Power Quality Analyzer User Manual (479) submenu displays the list of trend recording configurations (see § 5.9). This shortcut key lets you specify or modify the trend recording configurations.The following information is displayed:UNI-T UT285C Power Quality Analyzer User Manual (480)Proceed as follows to configure a recording:Example for configuration 1:★ Press the yellow key corresponding to theUNI-T UT285C Power Quality Analyzer User Manual (481) icon. It is displayed on a yellow ground.★ Select values by moving the yellow cursor using theUNI-T UT285C Power Quality Analyzer User Manual (482)or UNI-T UT285C Power Quality Analyzer User Manual (483) and UNI-T UT285C Power Quality Analyzer User Manual (484)or UNI-T UT285C Power Quality Analyzer User Manual (485) keys, then pressUNI-T UT285C Power Quality Analyzer User Manual (486)to validate. The red solid dot indicates validation.Reminder: You can record the following values:
UnitDesignation
TermsRMS phase-to-phase voltage(2φ, 3φ).
UtdTotal harmonic distortion of the phase-to-phase voltage(2φ, 3φ).
UcfCrest (peak) factor of phase-to-phase voltage(2φ, 3φ).
UubPhase-to-Phase voltage unbalance(2φ, 3φ).
HzNetwork frequency.
VrmsRMS phase-to-neutral voltage.
LtdTotal harmonic distortion of the phase-to-neutral voltage.
IfCrest factor of phase-to-neutral voltage.
VungPhase-to-neutral voltage unbalance(2φ, 3φ).
PSTShort-term flicker.
ArmsRMS current.
AddTotal harmonic distortion of the current.
ActCrest factor of current.
AuntCurrent unbalance(2φ, 3φ).
KFK factor.
WActive power.
VARReactive power.
VAApparent power.
PFPower factor.
CosφThe phase shift of power factor.
TanφTangent.
?See the comment below.
Features specific to the last two lines.These are recalled below:UNI-T UT285C Power Quality Analyzer User Manual (487)UNI-T UT285C Power Quality Analyzer User Manual (488)

These two lines involve the recording of Vah, Ah, Vh, and Uh variable harmonics. You can select the ranks of harmonics to be recorded (between 0 and 50) for each of these harmonics and odd-only harmonics within this range. Proceed as follows:

  • To enter the value to be recorded: with line o? highlighted in yellow, pressUNI-T UT285C Power Quality Analyzer User Manual (489). The arrowsUNI-T UT285C Power Quality Analyzer User Manual (490) appear. Select the value (Vah, Ah, Vh, and Uh) for which harmonics are to be recorded by pressing UNI-T UT285C Power Quality Analyzer User Manual (491)or UNI-T UT285C Power Quality Analyzer User Manual (492) . The red solid dot identifies your selection.Confirm by pressingUNI-T UT285C Power Quality Analyzer User Manual (493). The values field is highlighted in yellow.
  • To select the starting harmonic order: with the field highlighted in yellow, pressUNI-T UT285C Power Quality Analyzer User Manual (494) . The arrowsUNI-T UT285C Power Quality Analyzer User Manual (495) appear.
Select the order in which the harmonics are to be recorded by pressing UNI-T UT285C Power Quality Analyzer User Manual (496)or UNI-T UT285C Power Quality Analyzer User Manual (497) , then validate by pressing UNI-T UT285C Power Quality Analyzer User Manual (498). Press UNI-T UT285C Power Quality Analyzer User Manual (499)or UNI-T UT285C Power Quality Analyzer User Manual (500)go to the next field.
  • To select the last harmonic: with the second field (greater than or equal to the starting harmonic order) highlighted in yellow, pressUNI-T UT285C Power Quality Analyzer User Manual (501). Select the highest harmonic order to be recorded by pressingUNI-T UT285C Power Quality Analyzer User Manual (502)or UNI-T UT285C Power Quality Analyzer User Manual (503) , then validate by pressingUNI-T UT285C Power Quality Analyzer User Manual (504) . Press UNI-T UT285C Power Quality Analyzer User Manual (505)or UNI-T UT285C Power Quality Analyzer User Manual (506) go to the next field.
 For the odd harmonics only:To select or deselect this function, pressUNI-T UT285C Power Quality Analyzer User Manual (507). The red solid dot identifies your selection:★ selected, only odd harmonics between the two orders of harmonics specified in the previous points are recorded.★ not selected, all harmonics (even and odd) between the two orders of harmonics specified in the previous points are recorded.10.4. Viewing the recording listTheUNI-T UT285C Power Quality Analyzer User Manual (508) submenu displays recordings already made. Press the yellow key corresponding to theUNI-T UT285C Power Quality Analyzer User Manual (509) icon to see the list.The following data is displayed:UNI-T UT285C Power Quality Analyzer User Manual (510)

10.5. Deleting recordingsTheUNI-T UT285C Power Quality Analyzer User Manual (511)submenu is used to delete recordings. Proceed as follows:★Select the recording to be deleted using the UNI-T UT285C Power Quality Analyzer User Manual (512)or UNI-T UT285C Power Quality Analyzer User Manual (513)keys. The selected field is bolded.★Select the submenu by pressing the yellow key corresponding to theUNI-T UT285C Power Quality Analyzer User Manual (514)icon. The UNI-T UT285C Power Quality Analyzer User Manual (515)icon displayed yellow indicates ready to delete, then press the yellow key corresponding to the icon to cancel the delete state.The icon displayed in grayUNI-T UT285C Power Quality Analyzer User Manual (516)indicate doesn't delete.★In the state of ready to delete, pressUNI-T UT285C Power Quality Analyzer User Manual (517) to validate the deletion.

UNI-T UT285C Power Quality Analyzer User Manual (518)10.6. Viewing the records10.6.1. Characteristics of the recordUNI-T UT285C Power Quality Analyzer User Manual (519)10.6.2. Trend curvesUNI-T UT285C Power Quality Analyzer User Manual (520)

Remark: Values of the cursor are dashes “----” indicate errors or missing values in the record.The display period of this curve is 20 seconds. Since the period of the record is one second, each point of this curve corresponds to a value recorded in a one-second window once 20 seconds. There is therefore a substantial loss of information (19 values out of 20), but the display is rapid.With the increase in the display period, the loss values will be more. In this case, the user can select to activate the MIN-AVG-MAX mode. After the MIN-AVG-MAX mode is activated, each point of the curve represents the mean of the total sampling points every period(such as the display period is 20 seconds, the sampling period is 1 second, eachdisplay point of the curve represents the mean of 20 values recorded every second.).

UNI-T UT285C Power Quality Analyzer User Manual (521)

Figure 10-11: Vrms with MIN-AVG-MAX

With the MIN-AVG-MAX mode activated, each point of this curve represents the arithmetic mean of 60 values recorded. This display is therefore more precise because there is no loss of information, but it is slower(display timeUNI-T UT285C Power Quality Analyzer User Manual (522)With the MIN-AVG-MAX mode not activated, display the curve of 60 values recorded by the cursor, the display is rapid.UNI-T UT285C Power Quality Analyzer User Manual (523)UNI-T UT285C Power Quality Analyzer User Manual (524)This curve differs slightly from the previous one because, with the MIN-AVG-MAX mode, there is no loss of information. UNI-T UT285C Power Quality Analyzer User Manual (525)

Energy calculation steps:★ Press the yellow key corresponding to theUNI-T UT285C Power Quality Analyzer User Manual (526)icon to activate the energy summation mode. The current cursor time is the starting time of the energy calculation.★ Press theUNI-T UT285C Power Quality Analyzer User Manual (527)or UNI-T UT285C Power Quality Analyzer User Manual (528) to move the cursor. The stopping time of the energy calculation points to the cursor time, the device calculates the energy between the start time and stop time automatically.Note: the cursor moves left and cannot exceed the location of the starting time.

10.6.3. The needing time for display the curve in the different scales.The following table indicates the time needed to display the curve on the screen as a function of the width of the display window for a recording period of one second:
width of the display window 60 points or increments)Grid incrementTypical waiting time
5 days2 hours30 seconds
2.5 days1 hour15 seconds
15 hours15 minutes4 seconds
10 hours10 minutes2 seconds
5 hours5 minutes1 second
1 hour1 minute1 second
20 minutes10 seconds1 second
5 minutes5 seconds1 second
1 minute1 second1 second
★ to press theUNI-T UT285C Power Quality Analyzer User Manual (529)orUNI-T UT285C Power Quality Analyzer User Manual (530) key to change the scale of the display★ press the UNI-T UT285C Power Quality Analyzer User Manual (531)or UNI-T UT285C Power Quality Analyzer User Manual (532) key to move the cursor★ press theUNI-T UT285C Power Quality Analyzer User Manual (533)or UNI-T UT285C Power Quality Analyzer User Manual (534) key to change the display phase curve.But note that this may restart the loading/calculation of the values from the beginning.10.6.4. The longest recording time can be programmedThe longest time is based on the number of recording parameters selected and the sampling period, the typical condition is as follows:
parameter of selectedsampling periodThe typical longest time can be programmed
All parameters (total 123)1 second10 days
1~20 parameters1 second62 days
All parameters (total 123)5 seconds50 days
1~20 parameters5 seconds300 days
All parameters (total 123)1 minute600 days
1~20 parameters1 minute3600 days
The above table indicates that the selected parameters are fewer, the sampling period is greater, and the longest recording time is longer.

POWER AND ENERGY KEY

TheUNI-T UT285C Power Quality Analyzer User Manual (535) key displays power- and energy-related measurements.11.1. Available sub-menusThe sub-menus are listed on the screen below and described individually in the paragraphs that follow.The sub-menus are selected using the yellow keys on the keypad below the screen.UNI-T UT285C Power Quality Analyzer User Manual (536)11.2. Energy consumedTheUNI-T UT285C Power Quality Analyzer User Manual (537) sub-menu displays the active power, the reactive powers (capacitive and inductive), and the apparent we r.11.2.1. The energies consumed screen for the 3 phases (3L)This screen displays the following information:UNI-T UT285C Power Quality Analyzer User Manual (538)

UnitDesignation
WActive power.
WhActive energy consumed.
VARReactive power (inductiveUNI-T UT285C Power Quality Analyzer User Manual (539) or capacitiveUNI-T UT285C Power Quality Analyzer User Manual (540) ).
withReactive energies consumed (inductiveUNI-T UT285C Power Quality Analyzer User Manual (541) or capacitiveUNI-T UT285C Power Quality Analyzer User Manual (542) ).
VAApparent power.
VAApparent energy consumed.
11.2.2. The energies consumed screen for phase L1This screen displays the following information: UNI-T UT285C Power Quality Analyzer User Manual (543)
UnitDesignation
WActive power.
WhActive energy consumed.
VARReactive power (inductiveUNI-T UT285C Power Quality Analyzer User Manual (544) or capacitiveUNI-T UT285C Power Quality Analyzer User Manual (545) ).
withReactive energies consumed (inductiveUNI-T UT285C Power Quality Analyzer User Manual (546) or capacitiveUNI-T UT285C Power Quality Analyzer User Manual (547) ).
VAApparent power. (∑: sum of 3 phases)
VAApparent energy consumed.
PFPower factor.
CosφThe phase shift of the power factor
TanφTangent factor
φVAThe phase shift of phase-to-neutral voltage with respect to current.
Note: Filters L2 and L3 display the same information for phases 2 and 3. screen displays total power and energy consumed values for the 3 phases.11.3. Power factor display screenThis screen page is available only with the 3L filter. To display the information, press the yellow key on the keypad corresponding to theUNI-T UT285C Power Quality Analyzer User Manual (548) icon.The following data is displayed:UNI-T UT285C Power Quality Analyzer User Manual (549)11.4. The sum of energies consumed display screenTo display the information, select the icon of the right-hand filter. This screen displays the following information: UNI-T UT285C Power Quality Analyzer User Manual (550)
UnitDesignation
DTotal active power.
WTotal active energy consumed.
TTotal reactive power, inductive UNI-T UT285C Power Quality Analyzer User Manual (551)or capacitiveUNI-T UT285C Power Quality Analyzer User Manual (552).
WhTotal reactive energies consumed, inductiveUNI-T UT285C Power Quality Analyzer User Manual (553)or capacitiveUNI-T UT285C Power Quality Analyzer User Manual (554).
TTotal apparent power.
VARTotal apparent energy consumed.
11.5. The arithmetic mean values of the power factor display screenTo display the arithmetic mean values for the 3 phases (for power factor, the phase shift of power factor, and tangent), select the icon of the right-hand button.This screen displays the following information:UNI-T UT285C Power Quality Analyzer User Manual (555)11.6. Energies generatedTheUNI-T UT285C Power Quality Analyzer User Manual (556) sub-menu displays the active power, the reactive powers (capacitive and inductive), the apparent power, and all associated energies generated.11.6.1. The energies generated screen for the 3 phases (3L)This screen displays the following information: UNI-T UT285C Power Quality Analyzer User Manual (557)
UnitDesignation
WActive power.
WhActive energies are generated.
VARTotal reactive power, inductive UNI-T UT285C Power Quality Analyzer User Manual (558)or capacitiveUNI-T UT285C Power Quality Analyzer User Manual (559)
withTotal reactive energies generated, inductiveUNI-T UT285C Power Quality Analyzer User Manual (560) or capacitive UNI-T UT285C Power Quality Analyzer User Manual (561)
VATotal apparent power.
VTotal apparent energy generated.
PFPower factor.
CosφThe phase shift of power factor.
TanφTangent factor.
φVAThe phase angle between voltage and current.
11.6.2. The energies generated display for phase L1This screen displays the following information:UNI-T UT285C Power Quality Analyzer User Manual (562)
UnitDesignation
WActive power.
WhActive energies are generated.
VARTotal reactive power, inductiveUNI-T UT285C Power Quality Analyzer User Manual (563) or capacitiveUNI-T UT285C Power Quality Analyzer User Manual (564).
withTotal reactive energies generated, inductiveUNI-T UT285C Power Quality Analyzer User Manual (565) or capacitiveUNI-T UT285C Power Quality Analyzer User Manual (566)
VATotal apparent power.
VATotal apparent energy generated.
PFPower factor.
CosφThe phase shift of power factor.
TanφTangent factor.
φVAThe phase angle between voltage and current.
Note: Filters L2 and L3 display the same information for phases 2 & 3. ∑ screen displays total power and energy generated values for the 3 phases.11.6.3. The sums of energies generated display screenTo display the information, select the ∑ icon.This page displays:★The total active power,★The total active energy generated,★The total reactive power, inductiveUNI-T UT285C Power Quality Analyzer User Manual (567) or capacitiveUNI-T UT285C Power Quality Analyzer User Manual (568),★The total reactive energies generated (inductiveUNI-T UT285C Power Quality Analyzer User Manual (569) and capacitiveUNI-T UT285C Power Quality Analyzer User Manual (570) ),★The total apparent power,★The total apparent energy generated.11.7. Starting energy meteringTo start metering, press the yellow key on the keypad corresponding to the icon:UNI-T UT285C Power Quality Analyzer User Manual (571)11.8. Stopping energy meteringTo stop energy metering, press the yellow key on the keypad corresponding to the UNI-T UT285C Power Quality Analyzer User Manual (572)icon. UNI-T UT285C Power Quality Analyzer User Manual (573)11.9. Reset of energy meteringTo reset metering, press the yellow key on the keypad corresponding to theUNI-T UT285C Power Quality Analyzer User Manual (574) icon, TheUNI-T UT285C Power Quality Analyzer User Manual (575) icon displayed yellow indicates ready to delete, then press the yellow key corresponding to theUNI-T UT285C Power Quality Analyzer User Manual (576) icon to cancel the delete state.In the state of ready to delete, press the key to confirm. All energy values (consumed and generated) are reset.Note: refer to the 4-quadrant power diagram in § 17.3.

SCREEN SNAPSHOT KEY

TheUNI-T UT285C Power Quality Analyzer User Manual (577) key can be used to:★Capture a maximum of 60 screens for future reference (see § 12.1).★display previously saved screen snapshots (see § 12.2).Saved screens may then be transferred to a PC using the USB.12.1. Screen snapshotsPressUNI-T UT285C Power Quality Analyzer User Manual (578) for approx. 3 seconds to shoot any screen (including theUNI-T UT285C Power Quality Analyzer User Manual (579),UNI-T UT285C Power Quality Analyzer User Manual (580),UNI-T UT285C Power Quality Analyzer User Manual (581),UNI-T UT285C Power Quality Analyzer User Manual (582),UNI-T UT285C Power Quality Analyzer User Manual (583),UNI-T UT285C Power Quality Analyzer User Manual (584)andUNI-T UT285C Power Quality Analyzer User Manual (585) mode screens).During the capture, theUNI-T UT285C Power Quality Analyzer User Manual (586) icon appears in the top left corner of the screen instead of the icon for the active mode (UNI-T UT285C Power Quality Analyzer User Manual (587),UNI-T UT285C Power Quality Analyzer User Manual (588),UNI-T UT285C Power Quality Analyzer User Manual (589),UNI-T UT285C Power Quality Analyzer User Manual (590),UNI-T UT285C Power Quality Analyzer User Manual (591),UNI-T UT285C Power Quality Analyzer User Manual (592) , UNI-T UT285C Power Quality Analyzer User Manual (593),). The active modeUNI-T UT285C Power Quality Analyzer User Manual (594) icon reappears when you release the key: the device has saved the image.Reminder: the device can save a maximum of 60 screen snapshots. If the user attempts to take the 61st screen snapshot, first, upload the pictures you need to the computer through USB, then delete the device’s snapshots before capturing new pictures. UNI-T UT285C Power Quality Analyzer User Manual (595)12.2. Handling of screen snapshotsThis handling concerns stored screen snapshots, i.e.:★Display the list of screen snapshots (see § 12.2.2).★Viewing of one of the screen snapshots (see § 12.2.3).★Deletion of one or more of the screen snapshots (see § 12.2.4).12.2.1. Available functionsTo enter screen snapshot mode, briefly press theUNI-T UT285C Power Quality Analyzer User Manual (596) key.Reminder: holding theUNI-T UT285C Power Quality Analyzer User Manual (597) key down for approximately 3 seconds triggers the screen snapshot function (See § 12.1).UNI-T UT285C Power Quality Analyzer User Manual (598)12.2.2. Viewing the list of snapshotsPress briefly to display this list. The screen presents the list of snapshots (see figure 12-2).12.2.3. Viewing a snapshot from the listTo view a snapshot, proceed as follows:★ PressUNI-T UT285C Power Quality Analyzer User Manual (599) . TheUNI-T UT285C Power Quality Analyzer User Manual (600) icon is active and the snapshot list screen is displayed (see figure 12-2).★ Select the snapshot to be viewed using theUNI-T UT285C Power Quality Analyzer User Manual (601)or UNI-T UT285C Power Quality Analyzer User Manual (602) and UNI-T UT285C Power Quality Analyzer User Manual (603)or UNI-T UT285C Power Quality Analyzer User Manual (604) keys. The date and time of the selected snapshot are bolded.★ PressUNI-T UT285C Power Quality Analyzer User Manual (605) to display the selected snapshot. The top left corner of the screen displays the icon, alternating with the icon corresponding to the active mode (such as harmonic mode).★ PressUNI-T UT285C Power Quality Analyzer User Manual (606)to return to the list of screen snapshots.12.2.4. Deleting a snapshot from the listUNI-T UT285C Power Quality Analyzer User Manual (607)To delete a snapshot, proceed as follows:From the list of snapshots (see Figure 12-2 for example).★ Select the snapshot to be deleted using the UNI-T UT285C Power Quality Analyzer User Manual (608)or UNI-T UT285C Power Quality Analyzer User Manual (609) and UNI-T UT285C Power Quality Analyzer User Manual (610)or UNI-T UT285C Power Quality Analyzer User Manual (611) keys. The date and time of the selected snapshot are bolded.★ Press the yellow key on the keypad corresponding to theUNI-T UT285C Power Quality Analyzer User Manual (612)icon, The UNI-T UT285C Power Quality Analyzer User Manual (613)icon displayed yellow indicates ready to delete, then press the yellow key corresponding to the UNI-T UT285C Power Quality Analyzer User Manual (614)icon to cancel the delete state.★ In the state of ready to delete, press theUNI-T UT285C Power Quality Analyzer User Manual (615)key to confirm.PressUNI-T UT285C Power Quality Analyzer User Manual (616) to delete the selected snapshot. The snapshot is deleted from the list.

HELP KEY

The UNI-T UT285C Power Quality Analyzer User Manual (617) key provides information about the functions and symbols used in the current display mode.The following information is displayed:UNI-T UT285C Power Quality Analyzer User Manual (618)

DATA UPLOADED TO THE COMPUTER

To install a program, use the CD, then follow the on-screen instructions. Then connect the device to the PC using the USB cord supplied with the device, start the device, then open the data software to click on the computer’s Power Quality Analyzer.exe. Wait for the software to automatically search and connect the device. For directions for using the data export software, refer to its user manual.Note: Note: The transfer does not delete the data, just copy it to the PC. At alarm/trend chart record/transient capture mode (pending or ongoing), the PC cannot read the data.

GENERAL SPECIFICATIONS

15.1. Housing

HousingRigid shell over-molded with a red thermo-adhesive elastomer.
Connectors5 voltage measurement sockets.
4 special current connectors.
One connector for the specific mains power unit.
One connector for the USB link.
One connector for the SD memory card. This connector is located in the battery compartment on the back of the device.
KeysFunction, navigation, and mode. Can be used with gloves on.
Hand strapLocated on the side of the device, use to operate more conveniently.
StandTo hold the device in an inclined position.
Battery coverTo access the battery, on the back of the instrument.
dimensionsOverall: 240×170×68mmScreen: 640×480 pixelsW×H: 118mm×90mm;Diagonal: 148mm
WeightHost: 1600 g (with battery).
15.2. Power supply 15.2.1. External mains power supply
Range for useInput AC100V-240V, 50Hz/60Hz, Output DC12V, Maximum output current 3A.
Maximum input power36VA
15.2.2. Battery supplyThe device can be used without a connection to mains power. The battery also makes it possible to use the device during power outages.
BatteryRechargeable lithium-ion battery pack 9.6V
Capacity4500 mAh
Lifeat least 500 charge-discharge cycles.
Charging currentapprox. 0.6A
Charging timeapprox. 8 hours
Service T°[0 °C ; 50 °C].
Charging T°[10 °C ; 35 °C].
Storage T°Storage ≤30 days:[-20 °C; 50 °C]
storage for 30 to 90 days:[-20 °C ; 40 °C].
storage for 90 days to 1 year: [-20 °C ; 30 °C].
15.2.3. Consumption
At 10% luminosity410 mA
At 50% luminosity490 mA
At 100% luminosity590 mA
15.3. Range for use 15.3.1. Environmental conditions15.3.1.1. Climatic conditionsThe following chart shows conditions relating to ambient temperature and humidityUNI-T UT285C Power Quality Analyzer User Manual (619)

Caution: at temperatures above 40°C, the device must be powered by the battery alone OR by the mains power unit alone; use of the device with both the battery AND the mains power unit is prohibited.15.3.1.2. AltitudeUse: [0 m; 2 000 m]Storage: [0 m; 10 000 m]15.3.2. Mechanical conditionsUnder IEC 61010-1, the device is regarded as a PORTABLE DEVICE (HAND-CARRIED).

  • Operating position: any position.
  • Reference position in operation: on a horizontal plane, resting on its stand or lying flat.
  • Rigidity (IEC 61010-1): the force of 30 N applied to any part of the housing, the device is supported (at 40°C).
  • Fall (IEC 61010-1): 1 m in presumed worst-case position; the requirement is no permanent mechanical damage and functional degradation.
  • Tightness: IP 50 as per NF EN 60529 A1 (IP2X electrical protection for the terminals).
15.3.3. EMC electromagnetic compatibility15.3.3.1. Immunity as per IEC 61326:1-2006
  • Immunity to electrostatic discharges (as per IEC 61000-4-2)
1stlevel:Severity:4 kV in contact
Requirements:CRITERION A
2ndlevel:Severity:8 kV in air
Requirements:CRITERION A
 Immunity to radiated fields (as per IEC 61000-4-3 and IEC 61000-4-8)
Severity: 10V.m
RequirementsCRITERION B
 Immunity to rapid transients (IEC 61000-4-4)
Severity:2 kV on voltage inputs and power supply
1 kV on current input
Requirements:CRITERION A
 Immunity to electric shocks (as per IEC 61000-4-5)
Severity2 kV on voltage inputs in differential mode
1 kV on voltage inputs in common mode
Requirements:CRITERION A
 Conducted RF interference (as per IEC 61000-4-6)
Severity:3 V on voltage inputs and power supply
Requirements:CRITERION A
 Voltage interruption (as per IEC 61000-4-11)
Severity:100% loss over one period of the power supply
Requirements: CRITERION A
15.3.3.2. Emissions as per IEC 61326:1-2006Class A equipment.15.4. User safety
  • Application of safety rules as per IEC standard 61010-1 (protective impedances on voltage inputs).
  • Pollution type 2.
  • Double insulation on UNI-T UT285C Power Quality Analyzer User Manual (620)/O with respect to earth ( symbol).
  • Double insulation between the voltage inputs and power supply and the other UNI-T UT285C Power Quality Analyzer User Manual (621)/O ( symbol).

FUNCTIONAL CHARACTERISTICS

16.1. Reference conditionsThis table indicates the reference conditions of the quantities to be used by default in the characteristics.

Ambient temperature(23±2)°C
Humidity (relative humidity40%~ 60%
Atmospheric pressure[860hPa~ 1060hPa]
Phase-to-neutral voltage[(50±1%) Vrms; (500±1%) Vrms] without DC (< 0.5 %)
Frequency of electrical network50Hz±0.1Hz, 60Hz±0.1Hz
Phase shift0° (active power ), 90° (reactive power)
Harmonics<0.1%
Voltage unbalance<10%
Voltage ratio1
Current ratio1
Power supplyBattery only
Electric field<1V/m
Magnetic field<40A/m
16.2. Electrical characteristics 16.2.1. Voltage input characteristics0 Vrms to 1000 Vrms AC+DC phase-to-neutral and neutral-to-earth.0 Vrms to 2000 Vrms AC+DC phase-to-phase. (on condition of compliance with 1000 Vrms with respect to earth in CAT III).16.2.2. Current input range008B current clamp: 10mA~ 10A.040B current clamp: 0.10A~ 100A.068B current clamp: 1.0A~ 1000A.Optional current transformer: device input current 1mA~ 500mA.16.2.3. Characteristics of the device alone (excluding the current sensor)Respectively introduce the following data (on the basis of base conditions and the ideal current sensors, perfectly linear, no phase shift).
MeasurementRangeDisplay resolutionThe maximum error in the range of the reference
Frequency40Hz~ 70Hz0.01Hz±(0.03)Hz
True RMS phase-to-neutral voltage1.0V~ 1000VMin resolution 0.1V±(0.5%+5dgt)
True RMS phase-to-phase voltage1.0V~ 2000VMin resolution 0.1V±(0.5%+5dgt)
DC voltage1.0V~ 1000VMin resolution 0.1V±(1.0%+5dgt)
True RMS current10mA~ 1000AMin resolution 1mA±(0.5%+5dgt)
The peak of phase-to-neutral voltage1.0V~ 1414VMin resolution 0.1V±(1.0%+5dgt)
The peak of phase-to-phase voltage1.0V~ 2828VMin resolution 0.1V±(1.0%+5dgt)
Current peak10mA~ 1414AMin resolution 1mA±(1.0%+5dgt)
Peak factor1.00~ 3.990.01±(1%+2dgt)
4.00~ 9.990.01±(5%+2dgt)
Active power0.000W~ 9999.9kWMin resolution 0.001W±(1%+3dgt)Cosφ≥0.8
±(1.5%+10dgt)0.2≤Cosφ<0.8
Reactive power, inductive or capacitive0.000VAR~9999.9kVARMin resolution 0.001VAR±(1%+3dgt) Sinφ≥0.5
±(1.5%+10dgt) .2≤Sinφ<0.5
Apparent power0.000VA~9999.9kVAMin resolution 0.001VA±(1%+3dgt)
Power factor-1.000~ 1.0000.001±(1.5%+3dgt)Cosφ≥0.5
±(1.5%+10dgt)0.2≤Cosφ<0.5
Active energy0.000Wh~9999.9MWhMin resolution 0.001Wh±(1%+3dgt)Cosφ≥0.8
±(1.5%+10dgt)0.2≤Cosφ<0.8
Reactive energy, inductive or capacitive0.000VARh~9999.9MVARhMin resolution 0.001VARh±(1%+3dgt)Sinφ≥0.5
±(1.5%+10dgt)0.2≤Sinφ<0.5
Papparent energy0.000VAh~9999.9MVAhMin resolution 0.001VAh±(1%+3dgt)
Phase angle-179°~ 180°±(2°)
Tanφ(VA≥50VA)-32.76~ 32.76Min resolution 0.001φ:±(1°)
The phase shift of power factor(PDF)-1.000~ 1.0000.001φ:±(1°)
Harmonic ratio(order 1 to 50) (Vrms>50V)0.0%~ 99.9%0.1%±(1%+5dgt)
Harmonic angle(Vrms>50V)-179°~ 180°±(3°) harmonics of order 1 to25
±(10°) harmonics of order 26 to 50
Total harmonic ratio (THD or THD-F)≤500.0%~ 99.9%0.1%±(1%+5dgt)
Distortion factor(DF or THD-R)≤500.0%~ 99.9%0.1%±(1%+10dgt)
Transformer K factor1.00~ 99.990.01±(5%)
3 phases unbalance0.0%~ 100%0.1%±(1%)

16.2.4. Current sensor characteristics (after linearization)Sensor errors are offset by a typical correction inside the device. This typical correction, applied to the phase and amplitude, depends on the type of sensor connected and detected automatically) and the gain in the current acquisition channel used.

Type of current sensorTrue RMS currentMax error of true RMS currentMax error of phase angleφ
008B current clamp10mA~ 99mA±(1%+3dgt)±(1.5°), Arms≥20mA
100mA~ 10.0A±(1%+3dgt)±(1°)
040B current clamp0.10A~ 0.99A±(1%+3dgt)±(1.5°)
1.00A~ 100A±(1%+3dgt)±(1°)
068B current clamp1.0A~ 9.9A±(2%+3dgt)±(3°)
10.0A~ 1000A±(2%+3dgt)±(2°)
Optional transformerInstrument input current1mA~ 500mAThe selected transformer error:±1%The selected transformer error:±(1°)

APPENDICES

17.1. Mathematic formulae 17.1.1. Network frequency and samplingSampling is controlled by (locked to) the network frequency so as to deliver 256 samples per cycle from 40 Hz to 70 Hz. This locking is essential for the calculations of reactive power, unbalance, and harmonic ratio and angles.The frequency is measured by analyzing ten consecutive positive-going zero crossings in the first voltage channel (V1) or first current channel (I1) after digital low-pass filtering and digital suppression of the DC component.The time of the zero crossing is determined precisely by linear interpolation between two samples to achieve a resolution better than 0.002%.The signals are acquired using a 16-bit converter and (for current acquisition) dynamic gain switches.

17.1.2. RMS values of half-cycle voltage and current (excluding neutral)Half-cycle RMS phase-to-neutral voltage of phase (i+1)UNI-T UT285C Power Quality Analyzer User Manual (622)Half-cycle RMS phase-to-phase voltage of phase (i+1)UNI-T UT285C Power Quality Analyzer User Manual (623)Half-cycle RMS current of phase (i+1)UNI-T UT285C Power Quality Analyzer User Manual (624)Note: these values are calculated for each half-cycle so as not to miss any fault. NechDemPer is the number of samples in the half cycle.17.1.3. Minimum and maximum half-cycle RMS values (excluding neutral) UNI-T UT285C Power Quality Analyzer User Manual (625)Note: The duration of the evaluation is left to the user’s discretion (reset by pressing theUNI-T UT285C Power Quality Analyzer User Manual (626) or UNI-T UT285C Power Quality Analyzer User Manual (627) key).17.1.4. Short-term flicker (excluding neutral)A method based on the IEC 61000-4-15 standard.The input values are half-cycle phase-to-neutral voltages. The value is updated every 10 minutes.17.1.5. Peak values (voltage and current)i = 3 ⇔ neutral(except Upp and Upm)UNI-T UT285C Power Quality Analyzer User Manual (628)Note: NechPer is the number of samples in the half cycle.17.1.7. RMS value (voltage and current)UNI-T UT285C Power Quality Analyzer User Manual (629)Note: NechSec is the number of samples in the second.17.1.8. Unbalances (voltage and current)These are calculated from the filtered RMS vector values (over one second) VFrms and AFrms (ideally the fundamental vectors of the signals). UNI-T UT285C Power Quality Analyzer User Manual (630)

17.1.9. Harmonic calculations (excluding neutral)These calculations are carried out by FFT (16 bits), 1024 points over four cycles, with a rectangular window (see IEC 1000-4-7). From the real parts bk and the imaginary parts ak, the harmonic factor is calculated for each order and for each phase (Vharm[3][51], Uharm[3][51], and Aharm[3][51]) with respect to the fundamental and the angles Vph[3] [51], Uph[3][51], and Aph[3][51] with respect to the fundamental.This calculation is carried out according to the following principle:

UNI-T UT285C Power Quality Analyzer User Manual (631)Fs: is the sampled signal at the fundamental frequency.Co : Co: is the DC component.K: is the number of the frequency spectrum (the order of the harmonic component isUNI-T UT285C Power Quality Analyzer User Manual (632)

17.1.10. Harmonic distortions (excluding neutral)Two global values giving the relative quantity of harmonics are calculated: the THD as a proportion of the fundamental (“THD-F”) and the DF as a proportion of the RMS value (“THD-R”). UNI-T UT285C Power Quality Analyzer User Manual (633)

Voltage harmonic distortion multiplied by current harmonic distortion equals apparent power harmonic ratio (VAharm[3][51]), voltage harmonic angle minus current harmonic angle equals power harmonic angle (VAph[3][51])17.1.11. K factorUNI-T UT285C Power Quality Analyzer User Manual (634)17.1.12. Sequence harmonicsNegative-sequence harmonics UNI-T UT285C Power Quality Analyzer User Manual (635)UNI-T UT285C Power Quality Analyzer User Manual (636)

17.1.13. LS powers (excluding neutral) UNI-T UT285C Power Quality Analyzer User Manual (637)Reactive powers are calculated using the filtered signals (without harmonics) in accordance with EDF (French national electricity company) rules or from the apparent and active powers (with harmonics). The choice of calculation is left up to the user.Total active power.

UNI-T UT285C Power Quality Analyzer User Manual (638)17.1.14. Power ratios UNI-T UT285C Power Quality Analyzer User Manual (639)Tangent.UNI-T UT285C Power Quality Analyzer User Manual (640)17.1.15. Energies (excluding neutral)◆Consumed energies (w[i] ≥ 0)Consumed active energy of phase (i+1)UNI-T UT285C Power Quality Analyzer User Manual (641)UNI-T UT285C Power Quality Analyzer User Manual (642)◆generated energies (w[i] < 0)

UNI-T UT285C Power Quality Analyzer User Manual (643)17.2. HysteresisHysteresis is a screening principle that is often used after the detection of a threshold stage in Alarm mode (See § 5.10) and in Inrush current mode (see § 6.3). A correct hysteresis setting avoids repeated changes of state when the measurement oscillates about the threshold.

17.2.1. Surge detectionWith a hysteresis of 2%, for example, the return level for surge detection is equal to (100% - 2%) or 98% of the reference voltage threshold.UNI-T UT285C Power Quality Analyzer User Manual (644)17.2.2. Undervoltage or blackout detectionWith a hysteresis of 2%, for example, the return level for Undervoltage detection is equal to (100% + 2%) or 102% of the Reef voltage threshold.UNI-T UT285C Power Quality Analyzer User Manual (645)

17.3. Four-quadrant diagramUNI-T UT285C Power Quality Analyzer User Manual (646)17.4. Mechanism for triggering transient capturesThe sampling rate is a constant of 256 samples per cycle. When a transient capture is started, each sample is compared to the sample from the preceding cycle. The preceding cycle defines the mid-point of the trigger envelope and is used as a reference. As soon as a sample is outside the envelope, the triggering event occurs; the representation of the transient is then captured by the device. The cycle preceding the event and the three following cycles are saved to memory. UNI-T UT285C Power Quality Analyzer User Manual (647)

17.5. Capture conditions in inrush current modeReminder: The capture depends on a triggering (start) event and a stop event. If a capture ends with a stop event or if the recording memory of the device is full, the capture stops automatically.The capture stop threshold is calculated as follows:[Stop threshold [A]] = [Start threshold [A]] × (100 – [stop hysteresis [%]]) ÷ 100Here are the conditions for triggering and stopping captures:

TriggeringchannelTriggering and stop conditions
AlTriggering condition <=> [Al half-cycle RMS value] > [Triggering threshold]Stop condition <=> [Al half-cycle RMS value] < [Stop threshold]
A2Triggering condition <=> [A2 half-cycle RMS value] > [Triggering threshold]Stop condition <=> [A2 half-cycle RMS value] < [Stop threshold]
A3Triggering condition <=> [A3 half-cycle RMS value] > [Triggering threshold]Stop condition <=> [A3 half-cycle RMS value] < [Stop threshold]
3ATriggering condition <=> [[the half-cycle RMS value of one current channel]> [Triggering threshold]Stop condition <=> [the half-cycle RMS values of all current channels] < [Stop threshold]

MAINTENANCE

18.1. Important recommendationFor maintenance, use only the spare parts specified. The manufacturer cannot be held liable for any accident that occurs following a repair not performed by its customer service department or by an approved repairer.18.2. Recharging the batteryThe battery charge is managed by the device when connected to the AC network via the mains power unit supplied.★ For safety reasons and to ensure the correct operation of the charger, the storage battery must be replaced with power off.★ Do not throw the battery into a fire.★ Do not expose the battery to a temperature in excess of 75°C.★ Do not short-circuit the terminals of the battery.★ When the battery is fully recharged, please remove the power adapter(if do not use an external power supply).18.3. Replacing the batteryFor safety reasons, advice that replaces the battery only with the original modelTo replace the battery, proceed as follows:★ To eliminate all risks of electric shock, disconnect the power supply cord and connected devices.★ Turn the device over.★ Use a cross screwdriver to unscrew the two quarter-turn screws on the back of the housing. Then open the battery cover.★ Gently remove the old battery, and replace a new original battery (To avoid damaging the battery connection, do not pull on the wires).★ Put the battery compartment cover back in place and screw the 2 quarter-turn screws back in.★ Reboot the device to confirm.Note: If the battery is disconnected, it must then be fully recharged, even if it is not replaced, so that the device will know the battery charge condition (this information is lost when the battery is disconnected.UNI-T UT285C Power Quality Analyzer User Manual (648)

Documents / Resources

UNI-T UT285C Power Quality Analyzer [pdf] User Manual
UT285C Power Quality Analyzer, Power Quality Analyzer, Quality Analyzer
UNI-T UT285C Power Quality Analyzer User Manual (2024)
Top Articles
Payment Options – PCU Manila
New Online Banking Experience is Here | LLCU
Spasa Parish
Rentals for rent in Maastricht
159R Bus Schedule Pdf
Sallisaw Bin Store
Black Adam Showtimes Near Maya Cinemas Delano
Espn Transfer Portal Basketball
Pollen Levels Richmond
11 Best Sites Like The Chive For Funny Pictures and Memes
Things to do in Wichita Falls on weekends 12-15 September
Craigslist Pets Huntsville Alabama
Paulette Goddard | American Actress, Modern Times, Charlie Chaplin
What's the Difference Between Halal and Haram Meat & Food?
R/Skinwalker
Rugged Gentleman Barber Shop Martinsburg Wv
Jennifer Lenzini Leaving Ktiv
Justified - Streams, Episodenguide und News zur Serie
Elektrische Arbeit W (Kilowattstunden kWh Strompreis Berechnen Berechnung)
Omni Id Portal Waconia
Kellifans.com
Banned in NYC: Airbnb One Year Later
Four-Legged Friday: Meet Tuscaloosa's Adoptable All-Stars Cub & Pickle
Model Center Jasmin
Ice Dodo Unblocked 76
Is Slatt Offensive
Labcorp Locations Near Me
Storm Prediction Center Convective Outlook
Experience the Convenience of Po Box 790010 St Louis Mo
Fungal Symbiote Terraria
modelo julia - PLAYBOARD
Poker News Views Gossip
Abby's Caribbean Cafe
Joanna Gaines Reveals Who Bought the 'Fixer Upper' Lake House and Her Favorite Features of the Milestone Project
Tri-State Dog Racing Results
Navy Qrs Supervisor Answers
Trade Chart Dave Richard
Lincoln Financial Field Section 110
Free Stuff Craigslist Roanoke Va
Stellaris Resolution
Wi Dept Of Regulation & Licensing
Pick N Pull Near Me [Locator Map + Guide + FAQ]
Crystal Westbrooks Nipple
Ice Hockey Dboard
Über 60 Prozent Rabatt auf E-Bikes: Aldi reduziert sämtliche Pedelecs stark im Preis - nur noch für kurze Zeit
Wie blocke ich einen Bot aus Boardman/USA - sellerforum.de
Infinity Pool Showtimes Near Maya Cinemas Bakersfield
Dermpathdiagnostics Com Pay Invoice
How To Use Price Chopper Points At Quiktrip
Maria Butina Bikini
Busted Newspaper Zapata Tx
Latest Posts
Article information

Author: Annamae Dooley

Last Updated:

Views: 6429

Rating: 4.4 / 5 (65 voted)

Reviews: 88% of readers found this page helpful

Author information

Name: Annamae Dooley

Birthday: 2001-07-26

Address: 9687 Tambra Meadow, Bradleyhaven, TN 53219

Phone: +9316045904039

Job: Future Coordinator

Hobby: Archery, Couponing, Poi, Kite flying, Knitting, Rappelling, Baseball

Introduction: My name is Annamae Dooley, I am a witty, quaint, lovely, clever, rich, sparkling, powerful person who loves writing and wants to share my knowledge and understanding with you.